2.5 WiringCAUTION!Consider temperature for external cables!Cables may experience temperature increase due to system heat dissi-pation. Thus the cabling specification must be chosen 5°C above ambienttemperature!CAUTION!Separate insulation areas!The system is specified for SELV/PELV environment. Devices, which areattached to the system must meet theses specifications. Installation andcable routing other than SELV/PELV specification must be separatedfrom the system’s equipment!2.5.1 Wiring CPU 01xThe System SLIO CPUs have a power module integrated. Terminals with spring clamptechnology are used for wiring. The spring clamp technology allows quick and easy con-nection of your signal and supply lines.Umax 240V AC / 30V DCImax 10ACross section 0.08 ... 1.5mm2 (AWG 28 ... 16)Stripping length 10mm1 Pin number at the terminal module2 Opening for screwdriver3 Connection hole for wireTerminal module terminalsDataWiring procedureVIPA System SLIO Basics and mountingWiring > Wiring CPU 01xHB300 | PS-CM | | en | 17-16 17