6 Alarm List6-1HW1484458HW14844586 Alarm ListAlarmNumberAlarmNameSubCodeMeaning Cause Remedy4605 SETTOOLERROR1 The difference between the current toolconstant and a new set value exceeded theallowable range (parameter set value).Setting error (1)Check the following settings.·Correct the job so that the setting value oftag is allowable value.·Set the allowance amount of the tool dataautomatic setting function maximumdeviation (S3C1192) to large value.4126 CANNOTEXECUTEAUTO PMT1 System error Softwareoperationerror occurred(1)Reset the alarm, and then try again.(2)If the alarm occurs again, save theCMOS.BIN in maintenance mode, andthen contact your YASKAWArepresentative about occurrence status(operating procedure).2 PBOX cannot be edited. Setting error (1)Check the following settings.·I/O status of the edit prohibit signalThe edit prohibit signal cannot input.3 The source job cannot be edited. Setting error (1)Check the following settings.·The prohibit status of source jobIf the source job is protected from editing,it cannot be edited.4 The converted job cannot be edited. Setting error (1)Check the following settings.·The prohibit status of converted jobIf the converted job is protected fromediting, it cannot be edited.5 The memory area for job area is insufficient. Softwareoperationerror occurred(1)Reset the alarm.(2)If the error occurs again, delete unusedjobs.(3)If the error occurs again after theprevious measures were executed,initialize the job file in the maintenancemode, and then load the saved job file. Inthat case, delete the unused jobs.(4)If the error occurs again though theprevious measures were executed, savethe CMOS.BIN in maintenance mode, andthen contact your YASKAWArepresentative about occurrence status(operating procedure).25/27