No.(Addr.Hex) Name Description ValuesF7-15(03F3) Communication SpeedSelectionSets the communication speed0: 10 Mbps10: 10 Mbps100: 100 Mbps101: 10 (Port 1)/100 Mbps (port 2)102: 100 (Port 1)/10 Mbps (port 2)Default: 10 <9>Range: 10; 100 to102 <9>F7-16(03F4) Communication LossTimeoutSets the timeout value for communication loss detection intenths of a second. A value of 0 disables the connectiontimeout.Example: An entered value of 100 represents 10.0 seconds.Default: 0.0Min.: 0.0Max.: 30.0F7-17(03F5) EtherNet/IP SpeedScaling Factor Sets the scaling factor for the speed monitor in EtherNet/IPClass ID 2AH Object.Default: 0Min.: -15Max.: 15F7-18(03F6)EtherNet/IP CurrentScaling FactorSets the scaling factor for the output current monitor inEtherNet/IP Class ID 2AH Object.Default: 0Min.: -15Max.: 15F7-19(03F7)EtherNet/IP TorqueScaling FactorSets the scaling factor for the torque monitor in EtherNet/IP Class ID 2AH Object.Default: 0Min.: -15Max.: 15F7-20(03F8)EtherNet/IP PowerScaling FactorSets the scaling factor for the power monitor in EtherNet/IP Class ID 2AH Object.Default: 0Min.: -15Max.: 15F7-21(03F9)EtherNet/IP VoltageScaling FactorSets the scaling factor for the voltage monitor in EtherNet/IP Class ID 2AH Object.Default: 0Min.: -15Max.: 15F7-22(03FA)EtherNet/IP TimeScalingSets the scaling factor for the time monitor in EtherNet/IPClass ID 2AH Object.Default: 0Min.: -15Max.: 15F7-23 toF7-32(03FB to0374)Dynamic OutputAssembly ParametersParameters used in Output Assembly 116. Each parametercontains a MEMOBUS/Modbus address. The valuereceived for Output Assembly 116 will be written to thiscorresponding MEMOBUS/Modbus address. AMEMOBUS/Modbus address value of 0 means that thevalue received for Output Assembly 116 will not be writtento any MEMOBUS/Modbus register.Default: 0F7-33 toF7-42(0375 to037E)Dynamic InputAssembly ParametersParameters used in Input Assembly 166. Each parametercontains a MEMOBUS/Modbus address. The value sent forInput Assembly 166 will be read from this correspondingMEMOBUS/Modbus address. A MEMOBUS/Modbusaddress value of 0 means that the value sent for InputAssembly 166 is not defined by the user, therefore theoption default register value will be returned.Default: 0<1> To start and stop the drive with the EtherNet/IP master device using serial communications, set b1-02 to 3 orset the “Net Control” bit in the assemblies or Control Supervisor Object. To control the drive frequency referenceof the drive via the master device, set b1-01 to 3 or set the Net Reference bit in the assemblies or AC/DC Object.<2> When set to 3, the drive will continue to operate when a fault is detected. Take safety measures, such as installingan emergency stop switch.<3> Parameter setting value is not reset to the default value when the drive is initialized.6 Related Drive Parameters32 YASKAWA TOEP YAICOM 15A V1000 Option Dual-Port EtherNet/IP SI-EN3D/V Installation Manual