036-21122-002 Rev. B (0103)20 Unitary Products GroupMultipliers for determining the performance with other indoor sections.NOTE: For dry bulb temperatures different than those listed (between 73-87 F), sensible capacity increases by 1060 BTUH per 1000 CFM per degree above thelisted temperature and decreases by 1060 BTUH per 1000 CFM per degree belowthe listed temperature.COOLING PERFORMANCE DATAAIR CONDITIONER MODEL NO. HABA-(T,W)090SINDOOR COIL MODEL NO. KDBC-S090CONDENSERENTERING AIRTEMPERATUREID CFM 2400 3000 3600ID DB (°F) 85 80 70 85 80 70 85 80 70ID WB (°F) 72 67 57 72 67 57 72 67 5775T.C. 104.2 97.2 90.1 108.1 100.5 92.8 112.1 103.8 95.5S.C. 76.5 71.0 65.6 78.7 72.8 66.9 81.0 74.6 68.2K.W 8.30 8.21 8.13 8.33 8.25 8.18 8.36 8.29 8.2385T.C. 99.1 92.4 85.8 102.0 94.7 87.5 104.8 97.0 89.1S.C. 72.5 67.4 62.3 74.0 68.4 62.8 75.5 69.4 63.4K.W 8.97 8.86 8.75 9.01 8.90 8.79 9.04 8.94 8.8495T.C. 94.0 87.7 81.5 95.8 89.0 82.1 97.5 90.1 82.7S.C. 68.6 63.8 59.0 69.3 64.0 58.7 70.0 64.2 58.5K.W 9.64 9.50 9.37 9.68 9.55 9.41 9.72 9.59 9.45105T.C. 88.2 82.2 76.1 89.8 83.9 77.9 91.4 85.6 79.7S.C. 68.7 63.7 58.7 69.2 64.3 59.4 69.8 64.9 60.1K.W 10.33 10.14 9.96 10.38 10.21 10.03 10.43 10.27 10.10115T.C. 82.5 76.6 70.8 83.9 78.8 73.8 85.3 81.0 76.7S.C. 59.9 55.4 50.9 60.2 56.3 52.4 60.5 57.2 53.9K.W 11.02 10.79 10.55 11.08 10.87 10.65 11.14 10.95 10.76125T.C. 76.7 71.1 65.5 78.0 73.8 69.6 79.2 76.5 73.7S.C. 55.5 51.2 46.8 55.7 52.4 49.2 55.8 53.7 51.6K.W 11.71 11.43 11.15 11.78 11.53 11.28 11.86 11.63 11.41NOTE: ALL CAPACITIES ARE NET WITH INDOOR FAN HEAT ALREADY DEDUCTED AT 1250 BTUH/1000 CFM.Coil T.C. S.C. KWG2FD090(S,H)35 1.01 1.01 1.01