036-21548-001-D-0405Unitary Products Group 9TABLE 4: DNZ030 COOLING CAPACITIES - 2-1/2 TONTEMPERATUREOF AIR ONCONDENSER COILAIR ON EVAPORATOR COIL1,000 CFM 1,250 CFMWB °F WB °F72 67 62 57 72 67 62 5785 °FNET CAP. MBH 32.7 31.0 28.7 28.7 33.3 31.6 29.2 29.2TOTAL POWER kW 2.10 2.10 2.10 2.09 2.28 2.29 2.29 2.27Sensible CapacityMBH 1Entering DryBulb °F86 22.2 27.8 28.7 28.7 25.7 31.6 29.2 29.283 19.3 24.9 28.7 28.7 21.9 28.2 29.2 29.280 16.4 22.0 27.2 28.7 18.2 24.4 29.2 29.277 13.5 19.0 24.3 25.8 14.5 20.7 25.4 25.574 10.5 16.1 21.4 22.9 10.8 17.0 21.7 21.871 -- 13.2 18.5 20.0 -- 13.2 18.0 18.068 -- 10.3 15.6 17.1 -- 9.5 14.2 14.395 °FNET CAP. MBH 31.2 29.2 26.6 26.8 31.8 29.7 27.2 27.4TOTAL POWER kW 2.36 2.36 2.35 2.33 2.55 2.54 2.53 2.51Sensible CapacityMBH1Entering DryBulb °F86 21.8 27.3 26.6 26.8 25.2 29.7 27.2 27.483 18.9 24.4 26.6 26.8 21.5 27.7 27.2 27.480 15.9 21.5 26.3 26.8 17.8 24.0 27.2 27.477 13.0 18.6 23.4 23.9 14.1 20.3 23.4 23.774 10.1 15.7 20.5 21.0 10.3 16.5 19.7 19.971 -- 12.8 17.5 18.1 -- 12.8 16.0 16.268 -- 9.9 14.6 15.2 -- 9.1 12.3 12.5105 °FNET CAP. MBH 28.9 26.6 24.7 24.9 29.5 27.2 25.1 25.4TOTAL POWER kW 2.67 2.66 2.65 2.64 2.85 2.85 2.83 2.82Sensible CapacityMBH1Entering DryBulb °F86 21.0 25.7 24.7 24.9 24.6 27.2 25.1 25.483 18.1 23.4 24.7 24.9 20.9 26.1 25.1 25.480 15.2 20.5 24.5 24.9 17.2 23.2 25.1 25.477 12.3 17.6 21.6 22.0 13.4 19.5 21.4 21.774 9.3 14.7 18.7 19.1 9.7 15.8 17.7 18.071 -- 11.8 15.8 16.2 -- 12.1 14.0 14.268 -- 8.9 12.8 13.3 -- 8.3 10.2 10.5115 °FNET CAP. MBH 26.7 24.1 22.7 23.0 27.2 24.6 23.1 23.4TOTAL POWER kW 2.97 2.97 2.94 2.94 3.16 3.16 3.13 3.13Sensible CapacityMBH1Entering DryBulb °F86 20.2 24.1 22.7 23.0 24.0 24.6 23.1 23.483 17.3 22.5 22.7 23.0 20.3 24.6 23.1 23.480 14.4 19.5 22.7 23.0 16.6 22.5 23.1 23.477 11.5 16.6 19.8 20.1 12.8 18.7 19.4 19.774 8.6 13.7 16.9 17.2 9.1 15.0 15.6 16.071 -- 10.8 14.0 14.3 -- 11.3 11.9 12.368 -- 7.9 11.0 11.4 -- 7.6 8.2 8.5125 °FNET CAP. MBH 24.5 21.6 20.8 21.2 24.9 22.0 21.1 21.5TOTAL POWER kW 3.28 3.28 3.24 3.25 3.47 3.47 3.43 3.44Sensible CapacityMBH1Entering DryBulb °F86 19.5 22.5 20.8 21.2 23.4 22.0 21.1 21.583 16.5 21.5 20.8 21.2 19.7 23.0 21.1 21.580 13.6 18.6 20.9 21.2 15.9 21.7 21.1 21.577 10.7 15.6 18.0 18.2 12.2 18.0 17.3 17.874 7.8 12.7 15.1 15.3 8.5 14.3 13.6 14.071 -- 9.8 12.2 12.4 -- 10.5 9.9 10.368 -- 6.9 9.3 9.5 -- 6.8 6.2 6.61. These are net capacity ratings. The indoor blower motor heat has already been subtracted from the gross cooling capacity.ALL SENSIBLE CAPACITY