254599-YTG-C-080712 Unitary Products GroupTABLE 11: ELECTRICAL DATA - DF072 BELT DRIVE W/O POWERED CONV. OUTLETMODELTONNAGE VOLTAGECOMPRESSORS OD FANMOTORFLAIDBLOWERMOTORFLACONVOUTLETFLAELECTRIC HEATERMODEL NO.HEATERKWHEATERAMPSMIN.CIRCUITAMPACITY(AMPS)MAX. FUSE/BRKR 1SIZE(AMPS)RLAEACHLRAEACHDF072(6.0)208-3-60 20.7 156.0 2.3 5.2 0.0None - - 33.4 452CE04510525 2 4 11.1 33.4 452CE04510725 2 5.6 15.5 33.4 452CE04511025 8 22.2 34.3 452CE04511525 11.9 33.0 47.8 502CE04512025 15.9 44.1 61.7 702CE04513025 22.2 61.6 83.5 90230-3-60 20.7 156.0 2.3 5.2 0.0None - - 33.4 452CE04510525 2 5.3 12.7 33.4 452CE04510725 2 7.5 18.0 33.4 452CE04511025 10.6 25.5 38.4 502CE04511525 15.9 38.2 54.3 602CE04512025 21.2 51.0 70.2 802CE04513025 29.6 71.2 95.5 100460-3-60 10.0 75.0 1.3 2.6 0.0None - - 16.4 252CE04510746 2 6.8 8.2 16.4 252CE04511046 2 10.1 12.1 18.4 252CE04511546 2 13.6 16.4 23.7 252CE04512046 2 19.5 23.5 32.6 352CE04513046 2 28.8 34.6 46.6 50575-3-60 8.2 54.0 1.3 2.0 0.0None - - 13.3 202CE04511058 10.6 10.2 15.2 202CE04511558 15.9 15.3 21.6 252CE04512058 21.2 20.4 28 302CE04513058 30.4 29.3 39.1 401. HACR Type per NEC.2. These electric heaters do not include a fuse box. If a fuse box is required to meet a local code (i.e. Chicago), the fuse blockaccessories 2FB04700825 and 2FB04700846 are available for field installation.TABLE 12: ELECTRICAL DATA - DF072 DIRECT DRIVE W/O POWERED CONV. OUTLETMODELTONNAGE VOLTAGECOMPRESSORS OD FANMOTORFLAIDBLOWERMOTORFLACONVOUTLETFLAELECTRIC HEATERMODEL NO.HEATERKWHEATERAMPSMIN.CIRCUITAMPACITY(AMPS)MAX. FUSE/BRKR 1SIZE(AMPS)RLAEACHLRAEACHDF072(6.0)208-3-60 20.7 156.0 2.3 10.6 0.0None - - 38.8 502CE04510525 2 4.0 11.1 38.8 502CE04510725 2 5.6 15.5 38.8 502CE04511025 8.0 22.2 41.0 502CE04511525 11.9 33.0 54.5 602CE04512025 15.9 44.1 68.4 702CE04513025 22.2 61.6 90.3 100230-3-60 20.7 156.0 2.3 10.6 0.0None - - 38.8 502CE04510525 2 5.3 12.7 38.8 502CE04510725 2 7.5 18.0 38.8 502CE04511025 10.6 25.5 45.1 502CE04511525 15.9 38.2 61.1 702CE04512025 21.2 51.0 77.0 802CE04513025 29.6 71.2 102.3 1101. HACR Type per NEC.2. These electric heaters do not include a fuse box. If a fuse box is required to meet a local code (i.e. Chicago), the fuse blockaccessories 2FB04700825 and 2FB04700846 are available for field installation.