036-21687-002-A-1105Unitary Products Group 13using CO2 sensors. It uses an inside CO2 sensor to per-form Demand Ventilation. It can also use an Outside CO2sensor to perform Differential Demand Ventilation. It usesa Patented Comfort Ventilation algorithm to provide com-fortable ventilation air temperature. The patented econo-mizer-loading algorithm will protect the equipment whenharsh operating conditions exist. Humidity in the occupiedspace or return duct can be monitored and controlled viahumidity sensors and the on-board connection for hot gasre-heat system. It uses the INTELLI-Start™ algorithm tomaximize energy savings by recovering the building fromthe Unoccupied Setpoints to the Occupied Setpoints justin time for the Occupied Time Period to begin. The Sim-plicity™ INTELLI-Comfort™ balances space temperature,ventilation air temperature, CO2 and humidity for ultimatecomfort.• Simplicity™ INTELLI-Comfort™ with MOD LINK CON-TROL - The York® Simplicity™ INTELLI-Comfort™ withMod Link control is factory installed. It includes all thefeatures of the INTELLI-Comfort™ control with an addi-tional control to translate communications from MOD-BUS to the BACnet MSTP protocol.• Novar® BAS CONTROL - The Novar® ETC-3 buildingautomation system controller is factory installed.Includes supply air sensor, return air sensor, dirty filterindicator switch, and air proving switch.• JOHNSON CONTROLS BAS CONTROL - The JohnsonControl YK-UNT-1126 building automation system con-troller is factory installed. Includes supply air sensor,return air sensor, dirty filter indicator switch, and air prov-ing switch.• CPC BAS CONTROL - The Computer Process ControlsModel 810-3060 ARTC Advanced Rooftop building auto-mation system controller is factory installed. Includessupply air sensor, return air sensor, dirty filter indicatorswitch and air proving switch.• HONEYWELL BAS CONTROL - The HoneywellW7750C building automation system controller is factoryinstalled. Includes air supply sensor, return air sensor,dirty filter indicator switch, and air proving switch.• SMOKE DETECTORS - (supply air & return air) Thesmoke detectors stop operation of the unit by interruptingpower to the control board if smoke is detected within theair compartment.• COIL GUARD - Customers can purchase a coil guard kitto protect the condenser coil from damage. This is not ahail guard kit.• STAINLESS STEEL HEAT EXCHANGER - For applica-tions in corrosive environments, this option provides afull stainless steel heat exchanger assembly.• STAINLESS STEEL DRAIN PAN - An optional rust-proof stainless steel drain pan is available to provideyears of trouble-free operation in corrosive environ-ments.• BOTTOM DRAIN CONNECTION - An optional bottomdrain connection is available for inside the curb connec-tions for applications in cold environments to reducefreezing drain lines.• PHASE MONITORS - Designed to prevent unit damage.The phase monitor will shut the unit down in an out-of-phase condition.• DIRTY FILTER SWITCH - This kit includes a differentialpressure switch that energizes the fault light on the unitthermostat, indicating that there is an abnormally highpressure drop across the filters. Factory installed optionor field installed accessory.• HINGED FILTER DOOR/“TOOLLESS” BLOWER ANDACCESS PANELS (not hinged) - This option allows foreasy access and maintenance.NOTE:Knobs are shipped inside the unit to prevent ship-ping damage. These must be field installed fortool-less operation.FIELD-INSTALLED ACCESSORIES• SINGLE INPUT ELECTRONIC ENTHALPY ECONO-MIZERS - Includes a slide-in / plug-in damper assemblywith fully modulating spring-return motor actuator capa-ble of introducing up to 100% outdoor air with nominal1% leakage type dampers.The enthalpy system contains one sensor that monitorsthe outdoor air and determines when the air is coolenough and dry enough to provide free cooling.The rainhood is painted to match the basic unit and mustbe field-assembled before installing.• MOTORIZED OUTDOOR AIR INTAKE DAMPER -Includes a slide-in / plug-in damper assembly with a 2-position, spring return motor actuator which opens tosome pre-set position whenever the supply air blower isoperating and will drive fully closed when the blower unitshuts down.The rain hood is painted to match the basic unit andmust be field assembled before installing.• ELECTRIC HEATERS wired for single point power sup-ply. These nickel chromium heater elements are pro-vided with limit and automatic reset capability to preventoperation at excessive temperatures.