66324-YIM-B-1004Unitary Products Group 114. All piping should be cleaned of dirt and scale by ham-mering on the outside of the pipe and blowing out theloose dirt and scale. Before initial start-up, be sure thatall of the gas lines external to the unit have been purgedof air.5. The gas supply should be a separate line and installed inaccordance with all safety codes as prescribed underLimitations. After the gas connections have been com-pleted, open the main shut-off valve admitting normalgas pressure to the mains. Check all joints for leaks withsoap solution or other material suitable for the purpose.NEVER USE A FLAME.6. The furnace and its individual manual shut-off valve mustbe disconnected from the gas supply piping system dur-ing any pressure testing of that system at test pressuresin excess of 1/2 psig (3.48 kPa).The furnace must be isolated from the gas supply piping sys-tem by closing its individual manual shut-off valve during anypressure testing of the gas supply piping system at test pres-sures equal to or less than 1/2 psig (3.48 kPa).FLUE VENT HOODThe flue vent hood with screen is not shipped attached. Thishood must be installed to assure proper unit operation. Thehood must be fastened to the outside of the side gas control/electrical compartment with the screws provided in the bagattached to the inside of the gas control/electrical compart-ment, see Figure 4.Flue hood surfaces may be hot.FIGURE 6 - FLUE VENT OUTLET AIR HOODThe flue exhaust hood must be properly installedand within the recommended clearances. Furthercommunications and action must be given to thehome or building owner(s) to eliminate any unau-thorized human contact around this area duringthe heating cycle. Flue hood surface and immedi-ate area are designed to operate at high tempera-tures during the heating cycle.VENTOUTLETSCREENFLUEVENTOUTLETAIRHOOD