036-21366-007-A-120516 Unitary Products GroupTABLE 10: SIDE SUPPLY AIR BLOWER PERFORMANCE - 208/230 VOLTS 1MODEL #DNPMODE(COOLING / HEATING) CFMEXTERNAL STATIC PRESSURE - IWG.20 .30 .40 .50 .60 .70 .80 .90 1.0WATTS WATTS WATTS WATTS WATTS WATTS WATTS WATTS WATTS030 COOLING(FACTORY SETTING) 1000 248 298 325 365 385 411 470 498 500030 COOLING(FIELD SETTING) 1250 342 385 431 474 510 562 614 657 694030 HEATING (2 TUBE)(FACTORY SETTING) 850 169 217 237 278 302 334 374 401 431030 HEATING (3 TUBE)(FACTORY SETTING) 1100 300 338 378 416 447 493 539 576 609036 COOLING(FACTORY SETTING) 1200 354 396 436 511 548 599 641 677 721036 COOLING(FIELD SETTING) 1350 442 503 563 606 648 685 721 774 826036 HEATING (2 TUBE)(FACTORY SETTING) 700 207 231 254 298 320 349 - - -036 HEATING (3 TUBE)(FACTORY SETTING) 1250 383 432 478 543 581 628 - - -036 HEATING (4 TUBE)(FACTORY SETTING) 1350 442 503 563 606 648 685 - - -042 COOLING(FACTORY SETTING) 1350 410 457 504 575 646 687 729 780 830042 COOLING(FIELD SETTING) 1500 450 500 553 641 729 798 830 872 939042 HEATING (3 TUBE)(FACTORY SETTING) 1500 450 500 553 641 729 798 830 872 939042 HEATING (4 TUBE)(FACTORY SETTING) 1275 388 433 478 545 612 652 691 739 787048 COOLING(FACTORY SETTING) 1400 427 476 525 599 673 716 759 812 865048 COOLING(FIELD SETTING) 1600 476 532 587 687 786 872 958 994 1030048 HEATING (3 TUBE)(FACTORY SETTING) 1525 458 511 564 654 744 814 - - -048 HEATING (4 TUBE)(FACTORY SETTING) 1600 476 532 587 687 786 872 - - -048 HEATING (5 TUBE)(FACTORY SETTING) 1600 476 532 587 687 786 872 - - -060 COOLING(FACTORY SETTING) 1500 439 526 559 636 716 748 816 884 941060 COOLING(FIELD SETTING) 1800 659 809 814 946 1001 1053 1124 1176 1180060 HEATING (3 TUBE)(FACTORY SETTING) 1500 439 526 559 636 716 748 816 884 941060 HEATING (4 TUBE)(FACTORY SETTING) 1700 576 757 788 872 929 979 1000 1121 1188060 HEATING (5 TUBE)(FACTORY SETTING) 1700 576 757 788 872 929 979 1000 1121 11881. Above data includes allowances for a dry coil, gas heat exchanger and no filters. For additional pressure drops, refer to Tables 11and 12.