343615-YTG-B-0308Johnson Controls Unitary Products 15TABLE 16: DY036 COOLING CAPACITIES (3 TON)Air on Evap-orator CoilTemperature of Air on Condenser Coil75°F 85°FCFM WB(°F)TotalCap. 1(MBH)Total 2Input(kW)Sensible Capacity (MBH) 1Return Dry Bulb (°F)TotalCap. 1(MBH)Total 2Input(kW)Sensible Capacity (MBH) 1Return Dry Bulb (°F)86 83 80 77 74 71 68 86 83 80 77 74 71 6890072 44 2.3 24 21 19 16 14 - - 41 2.5 23 20 18 15 12 - -67 42 2.3 30 28 25 23 20 18 15 38 2.5 29 26 24 21 18 16 1362 40 2.3 40 35 33 30 28 25 23 35 2.5 35 32 30 27 25 22 2057 39 2.3 39 37 35 32 30 27 25 35 2.5 35 34 31 28 26 23 21105072 44 2.2 26 23 20 17 14 - - 42 2.5 25 22 19 16 13 - -67 42 2.3 33 30 27 24 21 18 15 39 2.5 31 28 25 22 19 16 1362 40 2.3 40 38 35 32 29 26 23 35 2.5 35 34 32 29 26 23 2057 39 2.3 39 38 37 34 31 28 25 35 2.5 35 35 33 30 27 24 21120072 44 2.2 28 25 21 18 14 - - 43 2.5 27 24 20 17 13 - -67 43 2.3 35 32 28 25 21 18 14 40 2.5 34 31 27 24 20 17 1362 40 2.3 40 40 37 33 30 26 23 36 2.5 36 36 34 31 27 24 2057 39 2.3 39 39 39 36 32 29 25 36 2.5 36 36 36 32 29 25 22135072 45 2.2 30 26 22 18 14 - - 43 2.5 29 25 21 17 13 - -67 43 2.3 37 33 29 25 21 18 14 40 2.5 36 32 28 24 20 16 1262 41 2.3 41 41 39 35 31 27 23 37 2.5 37 37 36 32 28 24 2057 40 2.3 40 40 40 36 32 28 24 36 2.5 36 36 36 32 28 24 20150072 46 2.3 32 27 23 18 14 - - 44 2.5 31 27 22 18 13 - -67 44 2.3 40 35 31 26 22 17 13 41 2.5 39 34 30 25 21 16 1262 42 2.3 42 42 42 37 33 28 24 37 2.5 37 37 37 33 28 24 1957 41 2.3 41 41 41 36 32 27 23 37 2.5 37 37 37 32 28 23 1995°F 105°F90072 38 2.7 21 19 16 14 11 - - 35 3.0 20 17 15 12 10 - -67 35 2.7 27 24 22 19 17 14 12 31 2.9 25 23 20 18 15 12 1062 30 2.7 30 29 27 24 22 19 17 27 3.0 27 26 24 21 19 16 1457 30 2.7 30 30 27 25 22 19 17 27 3.0 27 27 25 22 20 17 15105072 39 2.7 24 21 18 15 12 - - 36 3.0 22 19 16 13 10 - -67 36 2.7 30 27 24 21 18 15 12 32 2.9 28 25 22 19 16 13 1062 31 2.7 31 31 30 26 23 20 17 28 2.9 28 28 26 23 20 17 1457 31 2.7 31 31 30 27 24 21 18 28 2.9 28 28 27 24 21 18 15120072 41 2.7 26 23 19 16 12 - - 37 2.9 25 21 18 14 11 - -67 37 2.7 33 30 26 23 19 16 12 33 2.8 31 28 24 21 17 14 1062 32 2.7 32 32 32 29 25 22 18 29 2.9 29 29 29 25 22 18 1557 32 2.7 32 32 32 29 25 22 18 29 2.9 29 29 30 26 23 19 16135072 41 2.7 28 24 20 16 12 - - 37 3.0 27 23 19 15 11 - -67 37 2.7 35 31 27 23 19 15 11 33 2.9 32 29 25 21 17 13 962 32 2.7 32 32 32 28 24 20 16 29 2.9 29 29 29 25 21 17 1357 33 2.7 33 33 33 29 25 21 17 29 2.9 29 29 30 26 22 18 14150072 42 2.7 30 26 21 17 12 - - 37 3.1 28 24 20 15 11 - -67 38 2.7 38 33 29 24 20 15 11 33 2.9 33 31 27 22 18 13 962 33 2.7 33 33 33 28 24 19 15 29 3.0 29 29 29 24 20 15 1157 33 2.7 33 33 33 29 24 20 15 29 3.0 29 29 29 25 20 16 11115°F 125°F90072 32 3.3 18 16 13 11 8 - - 28 3.7 17 14 12 9 7 - -67 27 3.1 23 21 18 16 13 11 8 24 3.3 22 19 17 14 11 9 662 24 3.2 24 23 21 18 16 13 11 21 3.5 21 20 18 15 13 10 857 25 3.2 25 25 23 20 17 15 12 22 3.5 22 22 20 18 15 13 10105072 32 3.3 21 18 15 12 9 - - 29 3.5 19 16 13 10 7 - -67 28 3.0 26 23 20 17 14 11 8 24 3.2 24 22 18 15 12 9 662 25 3.1 25 24 23 20 17 14 11 21 3.4 21 21 20 17 14 11 857 25 3.1 25 25 25 22 19 16 13 22 3.4 22 22 22 19 16 13 10120072 33 3.2 23 20 16 13 9 - - 29 3.4 21 18 14 11 7 - -67 29 3.0 29 26 22 19 15 12 8 25 3.1 25 24 20 17 13 10 662 25 3.1 25 25 25 22 18 15 11 22 3.3 22 22 22 18 15 11 857 26 3.1 26 26 27 24 20 17 13 22 3.3 22 22 22 21 18 14 11135072 33 3.3 25 21 17 13 9 - - 29 3.6 23 19 15 11 7 - -67 29 3.1 29 27 23 19 15 11 8 24 3.2 24 24 21 17 13 10 662 25 3.2 25 25 25 21 17 13 9 21 3.4 21 21 21 17 13 9 557 26 3.2 26 26 26 22 18 14 10 22 3.4 22 22 22 19 15 11 7150072 33 3.4 27 22 18 13 9 - - 28 3.8 25 20 16 11 7 - -67 28 3.2 28 28 25 20 16 11 7 24 3.4 24 24 23 18 14 9 562 25 3.3 25 25 25 20 16 11 7 21 3.6 21 21 21 16 12 7 357 25 3.3 25 25 25 21 16 12 8 22 3.6 22 22 22 17 13 8 41. The capacities are gross ratings. For net capacity, deduct indoor blower motor, MBH=3.415 x kW. Refer to the appropriate Blower Perfor-mance table for the kW of the supply air blower motor.2. These ratings include the condenser fan motors (total 1 kW) and the compressor motors but not the supply air blower motor.
PreviousNext |