YORK INTERNATIONAL28Cooling Performance Data – 80 Ton ModelTABLE 8 – COOLING PERFORMANCE DATA* – 80 TON MODEL* Rated performance is at sea level. Cooling capacities are gross cooling capacity.35°C AIR ON CONDENSER COIL* Rated performance is at sea level. Cooling capacities are gross cooling capacity.29.4°C AIR ON CONDENSER COILCAPACITY (kW) AT ENTERING DRY BULB (°C)ENTERING 32 30 28 27 25 23m3/hr WB (°C) CAP SHC CAP SHC CAP SHC CAP SHC CAP SHC CAP SHC22 265 195 264 172 262 153 261 135 259 116 – –27184 19 248 224 244 204 244 186 243 167 241 149 240 13117 251 251 239 233 226 216 225 196 224 182 223 16222 272 207 270 181 269 160 267 140 266 120 – –30582 19 256 239 250 216 250 196 249 175 247 156 246 13617 259 259 251 250 237 236 231 208 230 192 229 17122 282 228 281 198 279 173 277 150 275 127 – –37378 19 272 268 261 240 260 216 259 191 257 167 255 14517 277 277 268 271 253 260 247 236 239 210 238 18522 290 252 289 216 287 187 285 160 283 133 – –45307 19 293 301 271 265 269 237 268 208 265 180 263 15417 298 298 278 281 264 271 267 274 247 230 246 200CAPACITY (kW) AT ENTERING DRY BULB (°C)ENTERING 32 30 28 27 25 23m3/hr WB (°C) CAP SHC CAP SHC CAP SHC CAP SHC CAP SHC CAP SHC22 256 192 254 168 253 150 252 131 250 112 – –27184 19 240 220 235 200 235 181 234 163 233 146 231 12717 243 243 231 225 226 216 218 193 215 177 215 15822 262 203 261 176 259 156 258 137 256 117 – –30582 19 247 235 242 212 241 191 240 171 239 152 237 13217 251 251 243 241 237 236 224 205 221 187 220 16722 272 224 271 193 269 169 267 146 265 123 – –37378 19 263 264 252 235 251 211 250 186 248 164 246 14017 268 268 259 262 253 260 239 233 230 204 230 18122 280 247 279 211 277 183 275 156 273 129 – –45307 19 284 296 262 260 259 232 258 202 256 176 254 14917 289 289 268 272 263 271 259 270 238 224 237 195