by johnson controls12Technical specificationsModel EUKCSizes 12 18 24 36 42 60CapacitiesCooling kW 3.5 5.0 7.0 10.0 12.0 16.0Heating kW 3.6 5.7 8.0 11.0 14.0 18.5Power Supply V.ph.Hz 230.1.50 230.1.50380.3.50 380.3.50Consumption Cooling / Heating kW 1.2 / 1.1 2.1 / 1.8 2.7 / 2.5 4.0 / 3.5 5.3 / 4.9 6.5 / 5.5Nominal flow m3/h 600 840 1 400 2 000 2 000 2 500Available pressure Pa 25 40 80 150 150 150Noise level (1 m.) dB (A) 36 / 38 / 40 38 / 40 / 42 40 / 42 / 44 46 / 48 / 50 46 / 48 / 50 48 / 50 / 53Dimensions (Height / Width / Depth) mm 220 / 913 / 680 266 / 1 012 / 736 268 / 1 270 / 504 290 / 1 251 / 744 290 / 1 251 / 744 330 / 1 251 / 788Nett Weight kg 27 36 37 57 57 66TubingGas diameter 1/2" 1/2" 5/8" 3/4” 3/4” 3/4”Liquid diameter 1/4" 1/4" 3/8" 1/2” 1/2” 1/2”Maximum tubing length m 20 20 30 50 50 50Maximum elevation tubing m 15 15 15 30 30 30Nominal cooling capacity is based on: Indoor air temp. = 27°C DB/19°C WB. Outdoor air temp. = 35°C DB, 5-meter tubing.Nominal heating capacity is based on : Indoor air temp. = 21°C DB - Outdoor air temp. = 7°C DB/6°C WB, 5-meter tubing.GBATTENTIONYour product is marked with this symbol. This means that at the end of its service life it should not be mixedwith other non-classified household waste. Therefore, disposal should be carried out in compliance with thecorresponding local and national regulations, in a correct and environment-friendly manner.The dismantling of the air conditioning unit, as well as the processing of refrigerant, oil and other components,should be carried out by a qualified technician and in compliance with the applicable legislation.Contact your local authorities for further informationAll data and dimensions are subject to change without prior notice.