261648-YTG-A-07068 Unitary Products GroupMultipliers for determining the performance with other indoor sections.NOTE: For dry bulb temperatures different than those listed (between 73-87 F), sensible capacity increases by 1060 BTUH per 1000 CFM per degree above thelisted temperature and decreases by 1060 BTUH per 1000 CFM per degree belowthe listed temperature.COOLING PERFORMANCE DATAAIR CONDITIONER MODEL NO. H1RA018S06INDOOR COIL MODEL NO. G1FA024S14,17CONDENSERENTERING AIRTEMPERATUREID CFM 550 650 750ID DB (°F) 85 80 70 85 80 70 85 80 70ID WB (°F) 72 67 57 72 67 57 72 67 5775T.C. 20.6 19.7 18.1 20.7 19.8 18.5 20.8 19.8 18.9S.C. 12.7 12.8 12.3 13.3 13.5 13.4 13.7 13.8 14.0K.W 1.68 1.65 1.64 1.72 1.71 1.70 1.75 1.74 1.7385T.C. 20.6 19.3 17.4 20.9 19.6 18.0 21.1 19.8 18.4S.C. 12.7 12.6 11.9 13.5 13.4 13.1 14.1 14.0 13.8K.W 1.58 1.54 1.53 1.62 1.59 1.58 1.65 1.63 1.6295T.C. 19.0 17.5 15.5 19.5 18.0 16.1 19.8 18.2 16.5S.C. 12.8 12.4 11.5 13.7 13.3 12.8 14.5 14.1 13.6K.W 1.97 1.91 1.90 2.02 1.96 1.95 2.05 2.00 1.99105T.C. 18.4 16.6 14.2 18.9 17.1 15.0 19.2 17.4 15.4S.C. 12.5 11.8 10.7 13.6 12.8 12.0 14.4 13.7 12.8K.W 1.82 1.77 1.75 1.88 1.82 1.80 1.91 1.86 1.83115T.C. 16.3 14.5 11.9 16.9 15.0 12.7 17.2 15.2 13.1S.C. 12.3 11.2 10.0 13.5 12.4 11.2 14.3 13.2 12.0K.W 2.24 2.19 2.14 2.31 2.24 2.19 2.35 2.28 2.22125T.C. 14.3 12.3 9.7 14.9 13.0 10.5 15.2 13.1 10.8S.C. 12.0 10.6 9.3 13.3 11.9 10.4 14.2 12.8 11.2K.W 2.66 2.61 2.53 2.74 2.66 2.58 2.79 2.70 2.61NOTE: ALL CAPACITIES ARE NET WITH INDOOR FAN HEAT ALREADY DEDUCTED AT 1250 BTUH/1000 CFMAir Handler Coil T.C. S.C. KWMA08B FC / MC18B 1.06 1.06 0.94MA08B G*FD024(S,H)17 1.06 1.06 0.94AHP18 - 0.97 0.97 1.02AHP24 - 1.06 1.08 0.93F*FP018 - 0.97 0.92 1.02F*FP024 - 0.97 0.97 1.02- FC/MC/PC/UC18B 1.06 1.06 0.94- G*FA030S14 1.06 1.06 0.94- G*FD024(S,H)17 1.06 1.06 0.94- HC18 1.06 1.06 0.94