5324339-YTG-D-1117Johnson Controls Unitary Products 11UNIT DIMENSIONS & ACCESS LOCATIONSModel Dimensions - in inchesA B CPCE6B36 51-1/4 45-3/4 49PCE6B48 51-1/4 45-3/4 53PCE6B60 51-1/4 45-3/4 55+,*+92/7$*(23(1,1*´+,*+92/7$*(23(1,1*´&2035(6625$&&(663$1(/&21'(16$7('5$,1 %/2:(5$&&(663$1(/ &21752/+($7$&&(663$1(//2:92/7$*(23(1,1*´+($76(&7,21$&&(663$1(/%$&$&2,/*8$5'UNIT CLEARANCESDirection Distance (in.) Direction Distance (in.)Top1 36 Power Entry (Right Side) 36Side Opposite Ducts 36 Left Side 24Duct Panel 0 Bottom 2,3 1NOTES:1. Minimum Clearance of 1inch all sides of supply air duct for the first 3 feet of duct for 20 & 25 kW., zero inches thereafter. For all other heaters, zero inch clearanceall sides for entire length of duct.2. Units must be installed outdoors. Overhanging structures or shrubs should not obscure outdoor air discharge outlet.3. Units may be installed on combustible floors made from wood or class A, B or C roof covering materials.Note: For units applied with a roof curb, the minimum clearance may be reduced from 1 inch to 1/2 inch between combustible roof curb material and this supply airduct.INDOOR BLOWER SPECIFICATIONSModel MotorHP RPM EFF. SF FramePCE6B36 1/2 Variable 0.8 1.0 48PCE6B48 1 Variable 0.8 1.0 48PCE6B60 1 Variable 0.8 1.0 48SOUND PERFORMANCEModel(Tons)Sound Rating1dB (A)Octave Band Centerline Frequency (Hz)125 250 500 1000 2000 4000 8000PCE6B36 74 58.5 61.8 65.4 66.5 60.7 54.8 49.8PCE6B48 74 63.5 63.9 62.3 65 64 54.1 46.6PCE6B60 76 72.3 65.0 63.9 64 60 55.5 49.0NOTES:1. Rated in accordance with AHRI Standard 270.