5291596-YTG-E-1117Johnson Controls Unitary Products 17ADDITIONAL STATIC RESISTANCESize (Tons) CFM Wet Indoor Coil Economizer11. The pressure drop through the economizer is greater for 100% outdoor airthan for 100% return air. If the resistance of the return air duct is less than0.25 IWG, the unit will deliver less CFM during full economizer operation.Filter pressure drop based on standard filter media tested at velocities not toexceed 300 ft/min.Filter/Frame Kit036 (3.0)700 0.01 0.00 0.04800 0.02 0.01 0.06900 0.03 0.01 0.081000 0.04 0.01 0.101100 0.05 0.01 0.131200 0.06 0.02 0.161300 0.07 0.03 0.171400 0.08 0.04 0.18042 (3.5)1100 0.02 0.02 0.041200 0.03 0.02 0.041300 0.04 0.02 0.051400 0.05 0.03 0.051500 0.06 0.04 0.061600 0.07 0.04 0.071700 0.07 0.04 0.081800 0.08 0.04 0.091900 0.09 0.05 0.102000 0.09 0.05 0.11048 (4.0)1100 0.02 0.02 0.041200 0.03 0.02 0.041300 0.04 0.02 0.051400 0.05 0.03 0.051500 0.06 0.04 0.061600 0.07 0.04 0.071700 0.07 0.04 0.081800 0.08 0.04 0.091900 0.09 0.05 0.102000 0.09 0.05 0.11060 (5.0)1100 0.02 0.02 0.041200 0.03 0.02 0.041300 0.04 0.02 0.051400 0.05 0.03 0.051500 0.06 0.04 0.061600 0.07 0.04 0.071700 0.07 0.04 0.081800 0.08 0.04 0.091900 0.09 0.05 0.102000 0.09 0.05 0.11NOTES:BOTTOM DUCT DIMENSIONS (Inches)Model A B C D E F36, 42, 48, 60 14 13.5 5 3.5 47.5 42REAR DUCT DIMENSIONS (Inches)Model A B36, 42, 48, 60 13.6 14$' ´&$%$ 6833/<$,5'8&75(7851$,5'8&7)(´9,(:/22.,1*83$7%277202)81,7+2/(´ZLWK´JURPPHWRSHQLQJIRUJDVSLSH+2/(´IRUKLJKYROWDJH+2/(´ IRUORZYROWDJH$ % $ $6833/<$,5'8&75(7851$,5'8&7127(6HH)LJXUHWLWOHG³8QLW'LPHQVLRQV´IRUVLGHKROHVL]HVRIHOHFWULFDODQGJDVOLQHV