288429-YIM-A-0307Unitary Products Group 15042(3.5) DEX1100 0.03 0.01 0.03 0.051200 0.04 0.02 0.03 0.061300 0.04 0.03 0.03 0.071400 0.04 0.04 0.03 0.081500 0.05 0.05 0.04 0.091600 0.06 0.06 0.05 0.10048(4.0) DEX1100 0.03 0.01 0.03 0.051200 0.04 0.02 0.03 0.061300 0.04 0.03 0.03 0.071400 0.04 0.04 0.03 0.081500 0.04 0.05 0.04 0.091600 0.04 0.06 0.05 0.101700 0.05 0.07 0.05 0.111800 0.05 0.07 0.06 0.111900 0.06 0.08 0.06 0.112000 0.07 0.08 0.07 0.12060(5.0) DEY1100 0.03 0.01 0.03 0.051200 0.04 0.02 0.03 0.061300 0.04 0.03 0.03 0.071400 0.04 0.04 0.03 0.081500 0.04 0.05 0.04 0.091600 0.04 0.06 0.05 0.101700 0.05 0.07 0.05 0.111800 0.05 0.07 0.06 0.111900 0.06 0.08 0.06 0.112000 0.07 0.08 0.07 0.121. The pressure drop through the economizer is greater for 100% outdoor air than for 100% return air. If the resistance of thereturn air duct is less than 0.25 IWG, the unit will deliver less CFM during full economizer operation.Table 10: Electric Heat Minimum Supply AirSize(Tons) Model VoltageMinimum Supply Air (CFM)Heater kW5.0 7.5 10.0 15.0 20.0 25.0024(2.0) DEX 208/230-1-60 630 630 800 - - -030(2.5) DEX 208/230-1-60 630 630 800 800 - -036(3.0) DEX208/230-1-60 1070 1070 1070 1070 - -208/230-3-60 1070 1070 1070 1070 - -460-3-60 1070 1070 1070 1070 - -042(3.5) DEX208/230-1-60 1225 1225 1225 1225 - -208/230-3-60 1225 1225 1225 1225 - -460-3-60 1225 1225 1225 1225 - -048(4.0) DEX208/230-1-60 - - 1200 1430 1430 1430208/230-3-60 - - 1200 1430 1430 1430460-3-60 - - 1200 1430 1430 1430060(5.0) DEY208/230-1-60 - - 1615 1615 1955 1955208/230-3-60 - - 1615 1615 1955 1955460-3-60 - - 1615 1615 1955 1955Table 9: Additional Static Resistance (Continued)Size(Tons) Model CFM Wet Indoor Coil Economizer 1 Filter/Frame Kit Electric HeatTable 11: Indoor Blower SpecificationsSize(Tons) Model MotorHP RPM Eff. SF Frame024(2.0) DEX 1/2 Variable 0.8 1.0 48030(2.5) DEX 1/2 Variable 0.8 1.0 48036(3.0) DEX 1/2 Variable 0.8 1.0 48042(3.5) DEX 3/4 Variable 0.8 1.0 48048(4.0) DEX 3/4 Variable 0.8 1.0 48060(5.0) DEY 1 Variable 0.8 1.0 48Table 12: Electric Heat MultipliersVoltage kW Capacity Multipliers 11. Electric heaters are rated at nominal voltage. Use this table todetermine the electric heat capacity for heaters applied atlower voltages.Nominal Applied240 208 0.75230 0.92480 460 0.92