505428-YTG-C-030912 Johnson Controls Unitary ProductsUnit Limitations1. Rated in accordance with ARI Standard 110, Range “A” Utilization Voltage.†. Low Ambient accessories are available to permit stable system operation at ambient temperatures down to 0°F.Condenser Unit limitationsSize(Tons) Model Unit Voltage Applied Voltage1 Outdoor DB TempCooling (°F)Indoor DB TempCooling (°F)Outdoor DB TempHeating (°F)Indoor DB TempHeating (°F)Min Max Max Min† Max Min Max Min Max Min090(7.5) PC208/230-3-60 187 252125 40 86 68 70 0 80 50460-3-60 432 504575-3-60 540 630090(7.5) YC208/230-3-60 187 252125 40 86 68 - - - -460-3-60 432 504575-3-60 540 630120 (10) PC208/230-3-60 187 252125 40 86 68 70 0 80 50460-3-60 432 504575-3-60 540 630120 (10) YC/YD208/230-3-60 187 252125 40 86 68 - - - -460-3-60 432 504575-3-60 540 630150(12.5) YC/YD208/230-3-60 187 252125 40 86 68 - - - -460-3-60 432 504575-3-60 540 630180 (15) PC/PD208/230-3-60 187 252125 40 86 68 70 0 80 50460-3-60 432 504575-3-60 540 630180 (15) YC/YD208/230-3-60 187 252125 40 86 68 - - - -460-3-60 432 504575-3-60 540 630240 (20) PC/PD208/230-3-60 187 252125 40 86 68 70 0 80 50460-3-60 432 504575-3-60 540 630240 (20) YC/YD208/230-3-60 187 252125 40 86 68 - - - -460-3-60 432 504575-3-60 540 630