036-21060-004-A-110212 Unitary Products GroupTABLE 1: CAPACITY RATINGS - COOLINGMODEL TOTAL OUTPUT KW/MBH TOTAL INPUTKW COP EER ELECTRIC HEAT NOMINAL CAPACITY KW300 85.2 / 293 35.4 2.4 8.3 18, 36, 54, 72TABLE 2: CAPACITY RATINGS - GAS HEATMODELDM300TOTAL OUTPUT kW/MBH TOTAL INPUT kW COP EER GAS HEAT RATINGS MBHINPUT MBH OUTPUTLOW HEAT 85.2 / 293 35.4 2.4 8.3 300 240HIGH HEAT 85.2 / 293 35.4 2.4 8.3 380 304TABLE 3: COOLING CAPACITIES - 87 KW(DM300) M 3 /SAir OnEvaporator CoilTemperature of Air on Condenser CoilOD Dry Bulb - 27 OD Dry Bulb - 35 OD Dry Bulb - 46TotalCap kW 1PowerInput kW 2Sensible1 Capacity TotalCapkW 1PowerInputkW 2Sensible1 Capacity TotalCapkW 1PowerInputkW2Sensible1 CapacityEntering Dry Bulb °C Entering Dry Bulb °C Entering Dry Bulb °Cm 3 /sec. WB 31 28 25 22 31 28 25 22 31 28 25 224.7223 108 24.8 68 51 33 - 101 27.3 67 49 32 - 88 32.0 62 45 28 -20 100 24.0 90 71 53 35 94 26.4 89 69 51 34 83 31.2 83 64 47 3017 94 23.5 94 94 74 55 90 25.9 90 89 72 53 79 30.5 79 77 66 4714 94 23.5 94 94 88 76 89 25.8 89 89 83 74 79 30.5 79 77 72 674.2523 106 24.6 64 48 32 - 100 27.1 63 46 31 - 86 31.8 58 42 27 -20 98 23.9 84 67 50 34 92 26.2 82 65 48 32 81 30.7 76 60 44 2817 91 23.2 91 87 69 52 86 25.5 86 84 67 50 76 30.0 76 75 62 4514 91 23.2 91 90 85 71 86 25.5 86 86 80 69 76 30.0 76 75 70 633.7823 104 24.5 60 45 31 - 98 26.9 58 44 30 - 85 31.6 54 40 26 -20 96 23.8 78 62 48 33 90 26.0 76 61 46 31 78 30.3 71 56 41 2717 88 23.0 88 80 65 50 83 25.1 83 79 63 48 73 29.5 73 72 58 4314 88 23.0 88 87 82 66 83 25.1 83 83 78 65 73 29.5 73 72 67 591. These capacities are gross ratings. For net capacity deduct the heat of the supply air blower motor MBH = 3.415 x kw. Refer to the appropriateBlower Performance table for the kw of the supply air blower motor.2. These ratings include the condenser fan motors and the compressor motors, but not the supply air blower motor.