036-21539-003-B-030554 Unitary Products GroupNOTE: A 1” clearance must be provided between any com-bustible material and the supply air ductwork for adistance of 3 feet from the unit.NOTE: The products of combustion must not be allowed toaccumulate within a confined space and recirculate.NOTE: Locate unit so that the vent air outlet hood is at least:• Three (3) feet above any force air inlet located within10 horizontal feet (excluding those integral to the unit).• Four (4) feet below, 4 horizontal feet from, or 1 footabove any door or gravity air inlet into the building.• Four (4) feet from electric and gas meters, regulatorsand relief equipment.NOTE: All entry holes should be field sealed to prevent rainwater entry into building.FIGURE 12 -UNIT DIMENSIONS DR180, 240 & 300 (FRONT VIEW)