036-21411-002-A-0204Unitary Products Group 17TABLE 16: ELECTRICAL DATA COOLING/ELECTRIC HEAT W/ DIRECT DRIVE DEE036MODELDEEPOWERSUPPLYHEATERACCESSORYMODELNUMBERSUPPLYAIRBLOWERMOTORFLAELECTRIC HEATERSMINIMUMCIRCUITAMPACITYMAXFUSESIZE 1AMPSMAX.SIZEHACR 2kW STAGES TOTALAMPS036208-1-602CE045005064.44.0 1 19.1 30.7 45 452CE04500706 5.6 1 27.1 39.4 45 452CE04501006 8.0 1 38.3 53.4 60 602CE04501506 11.9 2 57.4 77.3 80 802CE04502006 15.9 2 76.6 101.2 110 110230-1-602CE045005064.45.3 1 22.1 33.1 45 452CE04500706 7.5 1 31.3 44.6 45 452CE04501006 10.6 1 44.2 60.7 70 702CE04501506 15.9 2 66.0 88.3 90 902CE04502006 21.2 2 88.3 115.9 125 125208-3-602CE0450052534.44.0 1 11.0 24.3 35 352CE045007253 5.6 1 15.6 25.0 35 352CE04501025 8.0 1 22.1 33.1 35 352CE04501525 11.9 2 33.1 46.9 50 502CE04502025 15.9 2 44.2 60.7 70 70230-3-602CE0450052534.45.3 1 12.7 24.3 35 352CE045007253 7.5 1 18.0 28.1 35 352CE04501025 10.6 1 25.5 37.4 40 402CE04501525 15.9 2 38.2 53.3 60 602CE04502025 21.2 2 51.0 69.2 70 70460-3-602CE0450074632.26.8 1 8.2 13.0 15 152CE045010463 10.1 1 12.1 17.9 20 202CE045015463 13.6 1 16.4 23.2 25 252CE045020463 19.5 2 23.5 32.1 35 35575-3-602CE045010582.210.6 1 10.2 15.5 20 202CE04501558 15.9 1 15.3 21.9 25 252CE04502058 21.2 2 20.4 28.2 30 301. Dual element, time delay type.2. Standard circuit breakers may be used in Canada and on applications over 60 amps where the heaters are separately fused.3. These electric heaters DO NOT include a fuse box. If a fuse box is required to meet a local code (e.g. Chicago), the following fuseblock accessories are available for field installation (see Table 19).