5402847-UIM-A-091724 Johnson Controls Unitary ProductsADJUSTMENT OF MANIFOLD GAS PRESSURE &INPUT RATEInlet and manifold gas pressure may be measured by connecting the“U” tube manometer to the gas valve with a piece of tubing. Follow theappropriate section in the instructions below. Refer to Figure 28 for adrawing of the locations of the pressure ports on the gas valve.Turn gas off at the ball valve or gas cock on gas supply linebefore the gas valve. Find the pressure ports on the gasvalve marked Out P and In P.1. The manifold pressure must be taken at the port marked OUT P.2. The gas line pressure must be taken at the port marked IN P.3. Using a 3/32” (2.4 mm) Allen wrench, loosen the set screw by turn-ing it 1 turn counter clockwise. DO NOT REMOVE THE SETSCREW FROM THE PRESSURE PORT.Read the inlet gas pressureConnect the positive side of the manometer to the IN P Tap on the gasvalve. Do not connect any tubing to the negative side of the manometer,as it will reference atmospheric pressure. Refer to Figure 29 for connec-tion details.1. Turn gas and electrical supplies on and follow the operating instruc-tions to place the unit back in operation.Table 11: Gas Rate (CU FT/HR)Seconds For1 RevolutionSize of Test Dial Seconds For1 RevolutionSize of Test Dial1 Cu Ft 2 Cu Ft 5 Cu Ft 1 Cu Ft 2 Cu Ft 5 Cu Ft10 360 720 1800 50 72 144 36011 327 655 1636 51 71 141 35512 300 600 1500 52 69 138 34613 277 555 1385 53 68 136 34014 257 514 1286 54 67 133 33315 240 480 1200 55 65 131 32716 225 450 1125 56 64 129 32117 212 424 1059 57 63 126 31618 200 400 1000 58 62 124 31019 189 379 947 59 61 122 30520 180 360 900 60 60 120 30021 171 343 857 62 58 116 29022 164 327 818 64 56 112 28123 157 313 783 66 54 109 27324 150 300 750 68 53 106 26525 144 288 720 70 51 103 25726 138 277 692 72 50 100 25027 133 267 667 74 48 97 24328 129 257 643 76 47 95 23729 124 248 621 78 46 92 23130 120 240 600 80 45 90 22531 116 232 581 82 44 88 22032 113 225 563 84 43 86 21433 109 218 545 86 42 84 20934 106 212 529 88 41 82 20535 103 206 514 90 40 80 20036 100 200 500 92 39 78 19637 97 195 486 94 38 76 19238 95 189 474 96 38 75 18839 92 185 462 98 37 74 18440 90 180 450 100 36 72 18041 88 176 439 102 35 71 17842 86 172 429 104 35 69 17343 84 167 419 106 34 68 17044 82 164 409 108 33 67 16745 80 160 400 110 33 65 16446 78 157 391 112 32 64 16147 76 153 383 116 31 62 15548 75 150 375 120 30 60 15049 73 147 367Table 12: Inlet Gas Pressure RangeINLET GAS PRESSURE RANGENatural Gas Propane (LP)Minimum* 4.5” W.C. (1.12 kPa) 8.0” W.C. (1.99 kPa)Maximum 10.5” W.C. (2.61 kPa) 13.0” (3.24 kPa) W.C.