251933-YTG-J-1009Johnson Controls Unitary Products 55Electric Heat Minimum Supply AirSize(Tons) VoltageMinimum Supply Air (CFM)Heater kW5 7 10 15 20 30036(3.0)208/230-1-60 900 900 900 900 900 -208/230-3-60 900 900 900 900 900 -460-3-60 - 900 900 900 900 -600-3-60 - - 900 900 900 -048(4.0)208/230-1-60 1200 1200 1200 1200 1200 -208/230-3-60 1200 1200 1200 1200 1200 -460-3-60 - 1200 1200 1200 1200 -600-3-60 - - 1200 1200 1200 -060(5.0)208/230-1-60 1500 1500 1500 1500 1500 1500208/230-3-60 1500 1500 1500 1500 1500 1500460-3-60 - 1500 1500 1500 1500 1500600-3-60 - - 1500 1500 1500 1500Indoor Blower Specifications (Belt Drive)Size(Tons)Motor Motor Sheave Blower SheaveBeltHP RPM Eff. SF Frame Datum Dia.(in.) Bore (in.) Model Datum Dia.(in.) Bore (in.) Model036(3.0)1-1/2 1725 0.8 1.15 56 2.8 - 3.8 7/8 1VL44 6.0 1 AK64 A371-1/2 1725 0.8 1.15 56 4.0 - 5.0 7/8 1VP56 6.2 1 AK66 A39048(4.0)1-1/2 1725 0.8 1.15 56 2.8 - 3.8 7/8 1VL44 5.2 1 AK56 A361-1/2 1725 0.8 1.15 56 4.0 - 5.0 7/8 1VP56 5.7 1 AK61 A38060(5.0)1-1/2 1725 0.8 1.15 56 2.8 - 3.8 7/8 1VL44 5.2 1 AK56 A362 1725 0.8 1.15 56 4.0 - 5.0 7/8 1VP56 5.2 1 AK56 A38Power Exhaust SpecificationsModel Voltage Motor Motor Fuse Size CFM @0.1 ESPHP RPM 11. Motors are multi-tapped and factory wired for high speed.QTY LRA FLA MCA2PE04703025 208/230-1-60 1/2 1725 1 23.7 4.4 5.5 8 13502PE04703046 460-1-60 1/2 1725 1 4.1 1.7 2.1 5 1350Electric Heat MultipliersVoltage kW Capacity Multipliers11. Electric heaters are rated at nominal voltage. Use this table to determine the electric heatcapacity for heaters applied at lower voltages.Nominal Applied240 208 0.75230 0.92480 460 0.92600 575 0.92