York YH9FYH24BAH-A-X Service Manual
OpenNo gas leakage?5.Detach the charge hose6. from the service port, open 2-way valve and 3-way. Turnthe valve rod anticlockwiseuntil hitting lightly.In case of gas leakage, tighten parts of pipe connection. Ifleakage stops, then proceed 6. stepsIf it does not stop gas leakage, discharge whole refrigerants from the serviceport. After aring work again and vacuumize, ll up prescribedrefrigerant from the gas cylinder.Anti countercurrent jointGaugemanifold(for R410A)2-way valve Liquid Side3-way valve Gas SideVacuum pump(for R410A)Tube(for R410A)Close2-way valve3-way valveOpen 90O2-way valve3-way valve2-way valve3-way valveValve rod capValve rod capService port capTo prevent the gas leakage, turn the service port’s cap, the valve rod’s cap for 2-wayvalve and 3-way’s a little more than the point where the torque increases suddenly.After attaching the each caps, check the gas leakage around the caps.7.8.Step 1. Step 2.Step 3.Step 7.Step 6.Step 4.The power source must be exclusively used for air conditioner. (Over I0A)In the case of installing an air conditioner in a moist place, please install an ea-For installation in other places, use a circuit breaker as far as possible.Pipe cutting is carried out with a pipe cutter and burs must be removed.After inserting the are nut, aring work is carried out.If the refrigerant of the air conditioner leaks, it is necessary to discharge all therefrigerant. Vacuumize rst, thencharge the liquid refrigerant into air conditio-ner according to the amount marked on the name plate.Please do not let other cooling medium, except speci ed one (R410A), or airenter into the cooling circulation system. Otherwise, there will be abnormalhigh pressure in the system to make it crack and lead to personal injuries. Power Source Installation Cutting and Flaring Work of PipingFlare tooling die 1.Cut pipe 2.Remove burs3.Insert the are nutCAUTIONFlare tool for R410A Conventional are toolClutch-type clutch-type(Rigid-type) Wing-nut type (Imperial-type)A 0~0.5mm 1.0~1.5mm 1.5~2.0mmrth leakage breaker.4.Flare pipeLean Damage of are Crack Partial Too outsidetcerrocnItcerroC On DrainageIt becomeshigh midway.The gap with theground is too smalThere is the badsmell from a ditchIt waves.The end is imm-ersed in water.Please install the drain hose so as to be downward slope without fail.Please don’t do the drainage as shown below.Please pour water in the drain pan of the indoor unit, andis carried out surely to outdoor.In case that the attached drain hose is in a room, please apply heat insulation toLess than5cmcon rm that drainageit without fail.Check Items for Test RunPut check mark in boxesGas leak from pipe connecting?Heat insulation of pipe connecting?Are the connecting wirings of indoor and outdoor rmlyIs the connecting wiring of indoor and outdoor rmly xed?Is drainage securely carried out?Is the earth line securely connected?Is the indoor unit securely xed?Is power source voltage abided by the code?Is there any noise?Is the lamp normally lighting?Are cooling and heating (when in heat pump) performed normally?Is the operation of room temperature regulator normal?Please kindly explain to our customers how to operatethrough the instruction manual.Check for Installation and Test Runinserted to the terminal block?11+2= kgR410A2 kg2=1= BCDF EkgAThis product contains fluorinated greenhouse gases covered bythe Kyoto Protocol. Do not vent into the atmosphere.Refrigerant type:R410AGWP* value:1975GWP=global warming potentialPlease fill in with indelible ink,on the refrigerant charge label supplied with the product.The filled out label must be adhered in the proximity of the productcharging port (e.g. onto the inside of the stop value cover).A contains fluorinated greenhouse gases covered by the KyotoProtocolB factory refrigerant charge of the product: see unit name plateC additional refrigerant amount charged in the fieldD total refrigerant chargeE outdoor unitF refrigerant cylinder and manifold for chargingContains fluorinated greenhouse gasescovered by the Kyoto ProtocolRefrigerant charge label2-way valve3-way valveInstallations15 |
Related manuals for York YH9FYH24BAH-A-X
York YH9FYC18BAH-A-X Service Manual
York YH9FYC09BAH-A-X Service Manual
York YH9FXC24BAH--FX Service Manual
York YH9FXH12BAH FX Series Service Manual
York YOHC 12 Service Manual
York YKHC 18 Service Manual
York HP Series Service Manual
York YOCA-YOHA 12 Service Manual
York YUHA 18 FS Service Manual
York YKCA-YKHA 18 Service Manual
This manual is suitable for:
manualsdatabase
Your AI-powered manual search engine