5.3 Version without connection cables29.08.2013v_anchluss_ecblue_B.vsd124 5631 Cover for terminal compartment2 Cable glands (2 x M16)seal insert with two holes 5 mm for two cables applicable if necessary3 Do not loosen the safety screws from the housing!4 Connection control system5 Connection alarm relay and mains connection6 Status LEDProcedure:1. Remove the cover from the terminal compartment for the connection.2. Both cable entry points are in a sealed condition at delivery.– Turn in cable gland until seal breaks.– Unused entry points must be sealed!3. When using the seal insert for two cables it is not permissible to use the corresponding cablegland with only one cable.4. Insert and connect cables properly and ensure tightness of the cable glands.5. Attach connection cover again carefully in correct position before start-up.Attention!• Temperatures up to 80 °C can be present on the controller housing.• To connect, always use heat resistant wires or, as an alternative, silicon tubes.• Only use lines which can guarantee a permanent seal around the cable glands (pressure-resistant,dimensionally-stable, round-centred jacket; e.g. by means of gusset filling)! Lines with filling fleeceare not permissible because moisture can penetrate due to the capillary effect!• Make absolutely sure that different connections do not come into contact (e.g. by splaying or looseconnecting wires).• Remants from installation and foreign object may not remain on the inside!Assembly instructions ECblue Electrical installationL-BAL-F055D-GB 1634 Index 002 Part.-No.16/51