8 Enclosure8.1 Technical dataType(Part-No.)Rated cur-rentOutput{1}[A]Rated cur-rent(I fundamen-tal compo-nent @50 Hz)Input{2}[A]Recommen-ded motoroutput{3}[kW]Rated tem-perature[°C]max. linefuse{4}[A]max. heatdissipation{2}[W]Weight[kg]FSDM2.6(308214) 2.6 2.6(2.4) 1.1 50 6 40 2.5FSDM3.6(308215) 3.6 3.4(3.1) 1.5, 40 6 55 2.6FSDM5(308216) 5.0 4.8(4.5) 2.2 55 10 80 4.6FSDM7(308217) 7.0 6.4(6.0) 3.0 50 10 105 4.7FSDM8.5(308218) 8.5 7.8(7.2) 4.0 55 10 130 5.6FSDM12(308264) 12.0 11.0(9.9) 5.5 55 16 175 5.7FSDM17(308269) 17.0 15.3(14.1) 7.5 50 20 260 5.9FSDM25(308322)25.0 25.0(-) 11 40 35 480 12.3FSDM32(308324)32.0 27.6(25.7) 15 50 35 750 24.3FSDM39(308326)39.0 34.0(31.5) 18.5 55 50 900 26.1FSDM46(308328)46.0 46.0(-) 22,0 50 50 1050 26.1FSDM62(308330)62.0 62.0(-) 30,0 40 63 1250 26.1{1} Rated current output current indication rating plate @ rated voltage, @ rated temperature (cos φ 0.8 at the output).{2} At rated voltage (cos φ 0.8 at the output), values for different specifications on request.{3} Example for power of a 4 pole motor. For the dimension of the frequency inverter size the rated current of the motor iscrucial!{4} Max. line fuse on site (line protection fuse) according to EN 60204-1 Classification VDE0113 Part 1 (see also Assemblyinstructions / Electrical installation / Mains connection / Line protection fuse).Line voltage* 3 ~ 208...480 V (-15 up to +10 %), 50/60 HzNominal voltage 400 VMaximal output voltage approx. 95 % from ULineMaximal output frequency 50 Hz (1 - 120 Hz) **Edgefrequency 50 Hz (1 - 120 Hz) **U/f-characteristic curve linear (quadratic) **Switching frequency 8 kHz (10 / 16 kHz) **Rating switching frequency FSDM2.6...25: 8 kHzFSDM32...62: 6 kHzRampup time 20 sec (1 - 250 sec) **Rampdown time 20 sec (1 - 250 sec) **Current limit 120 % (100 - 130 %) **Power factor > 0.9Operating Instructions Icontrol Basic – model series FSDM2.6...62 EnclosureL-BAL-E160-GB 1701 Index 004 Part.-No.22/28