24 - EN3.11.3 TEMPERATURE PROFILE2In the advanced TEMPERATURE PROFILE 2menu you can influence the temperature ofthe different temperature profiles (WARM,NORMAL and COOL) which you can set inthe TASK MENU.First choose which temperature profile mode youwould like to use in the menu SET MODE 2:■ ADAPTIVE = The desired indoor temperaturevaries with the outdoor climate (adaptive comforttechnology);■ FIXED = The desired indoor temperature is fixedand does not depend on the outdoor climate.In the ADAPTIVE mode the unit uses the RMOT 5 fordetermining the desired indoor temperature. Youcan only influence this desired indoor temperatureby 1.5°C from the NORMAL setting by activating thetemperature profile COOL or WARM. The NORMALsetting is 21.5°C @ 0°C RMOT 5. For every °Cincrease in RMOT5 the temperature is adjusted by+0.11°C.If you choose the FIXED mode you can set thetemperature for each temperature profile in theFIXED PRESETS2 menu.TemperatureprofilesDefault valueFIXEDValue ADAPTIVEWARM 24°C / 76°F NORMAL +1.5°CNORMAL 20°C / 68°F -COOL 18°C / 64°F NORMAL -1.5°C3.11.4 UNITS2In the menu UNITS 2 you can change the displayedunits of the temperature and airflow rate.Menu item Default valueTEMPERATURE2 CELSIUSFLOW2 l/s3.11.5 SEASON DETECTION2To prevent the unit from counteracting withexternal heating (e.g. central heating) andcooling (e.g. air conditioner) units in thedwelling, the unit is equipped with a function todetect the current season. The detection is based onthe RMOT5. In the menu SEASON DETECTION 2 youcan set the RMOT5 temperature on which theHEATING SEASON2 and COOLING SEASON 2 willstart.By selecting the option STARTS NOW you can startthe season mode right away which will save thecurrent RMOT5 as the desired new season limit.Menu item Default valueHEATING LIMIT RMOT5 11°C / 51°FCOOLING LIMIT RMOT5 20°C / 68°F3.11.6 RF SETTINGS2,8In the RF SETTINGS 2,8 menu you can setthe control options of the RF-signals. Theset control option is the same for allconnected RF ancillaries.In the menu RF SENSOR PRIORITY 2,8 you can setwhen the unit will respond to a RF-signal:Menu item FunctionON The unit will respond tothe RF-signal in AUTO andMANUAL mode.AUTO ONLY The unit will only respond tothe RF-signal in AUTO mode.When the unit is switchedto manual mode the unit willignore the RF-signal.OFF The unit will ignore the RF-signal.In the menu RF SENSOR FUNCTION 2,8 you can sethow the unit will respond to a RF-signal:Menu item FunctionFLOW PROPORTIONAL The unit will translate thesignal from a RF sensor to acorresponding airflow betweenthe starting and maximal setairflow.FLOW PRESET The unit will translate thesignal from a RF sensor to oneof the preset airflows 8.2 This menu is only visible when the advanced mode is active.3 This menu is only visible when the ancillary is connected to the unit.5 RMOT = running mean outdoor temperature (average temperature overpast five days).8 This menu is only visible when the unit has RF functionality.