Automation Components, Inc.2305 Pleasant View Road | Middleton, WI 53562Phone: 1-888-967-5224 | Website: workaci.comPage 1PRECAUTIONS• Remove power before wiring. Never connect ordisconnect wiring with the power applied. Do notallow live wires to touch the circuit board.• An isolation transformer is recommended whenpowering the device with 24 VAC.• Do not run the wiring in any conduit with line voltage.• Failure to wire devices with the correct polarity whenusing a shared transformer may result in damage toany device powered by the shared transformer.• Do not remove the cover. All user features areaccessible from the outside of the unit.MEDIAThe MLP2 can be used to monitor the differential pressurein any application that uses dry air or inert gas.MOUNTING INSTRUCTIONSUsing the two #8 x 3/4” self drilling mounting screwssupplied by ACI, mount the unit vertically with the brassfittings pointing towards the ground. Attach the unit tothe mounting surface using the two mounting openings located on the top and bottom flanges. This ensures that anycondensation that may form in the tubing does not have an effect on the pressure sensor. If mounting the unit horizontally,a slight zero shift may occur and care must be taken to prevent moisture from building up in the sensor. For best results, alltubing lengths should be limited to a maximum length of 75 feet (23 meters).MLP2 SERIESInstallation & Operation InstructionsVersion 6.0I0000791FIGURE 1: DLP DIMENSIONSFRONTBOTTOMFIGURE 2: DIN RAIL MOUNTING0.09"(2.381 mm)0.38"(9.593 mm)0.36"(9.198 mm)3.50"(88.90 mm)1.35"(34.42 mm)2.10"(53.32 mm)ZERODIN RAILVIN|GND|OUTPhone: 1-888-967-5224Website: workaci.com