This document may be subject to change Side 17 of 27Temp. controlIn the ”Temp. control” menu it is possible to chose a room temperature where the unit stops inorder to avoid further cooling of the building if the primary heating shuts down.” ” indicates that the menu point flashes and can be set to another valueUse of t he CTS 600 panel :- pr ess ESC t o go one st ep back i n t he menu- pr ess qpt o move up or down i n a menu or t oadj ust an act i vat ed menu- pr ess ENTER t o act i vat e a menu- pr ess ENTER t o conf i r m a menu- pr ess OFF t o t ur n of f t he uni t- pr ess ON t o t ur n t he uni t onHEATINGSURFACETEMP.CONTROLAIREXCHANGEDEFROSTINLETCONTROLSERVICE ENTERPRESETOFFMANUALOFFROOMCONTROLThe unit stops at thisroom temperature (1-20°C) - - means that thefunction is unactive.- - should be chosen ifthe panel is placed in acold environment.SENSOR”EXTERNAL”SENSORPANELSENSOR”PANEL”PRIORITY”HP + EXT”PRIORITY”HF”ENTER ENTERENTERSENSOR”EXHAUST”ROOMLOW 10°CPRIORITYHP + EXTPRIORITY”OFF”Indicates which sensorthat needs to be thecontrolling one.PANEL T15 (PanelSensor)ROOM EXT: T10(Duct sensor)EXHAUST: T3 (Exhaust)AIRQUALITYOFF: ventilationwithout heating surfaceHP: ventilation onlywith heatrecoveryHP+EXT:ventilation withheatpump and heatingsurface activRESTARTOFFMODBUSADR 30Figure 12: The "Temp. control" menu