Set upInstallationPositioning of the unitATTENTIONWhen positioning the unit, you should always consider future services and maintenance.It must be easy to change filters, and it must, for instance, be possible to remove the heatexchanger, and to replace fans or other components.ATTENTIONAn open space of minimum 60 cm in front of the unit is recommended.ATTENTIONThe unit must be level to enable proper drainage from the condensate tray.The unit makes little noise and produces only weak vibrations, but you should still take into accountpotential vibrations that can spread from the unit to individual building components. In order toseparate the unit from its foundation, it is therefore recommended that you install vibration absorbersunder the unit. There should be approx. 10 mm distance to other building components and topermanent fixtures.Top unitMin. 20 cmMin. 50 cmMin. 60 cmService area in front of the unitATTENTIONIf you fit flashings above the unit, there must be enough space to remove these easily.Combi 302 Polar Top (English) BY NILAN13