60 CHAPTER 4: S WITCH INSTALLATIONFigure 38 Ground the switch when ground bar is available■ If there is no ground bar but earth nearby and the grounding body is allowedto be buried, you can simply hammer an angle iron or steel pipe no shorterthan 0.5 m into the earth. In this case, the yellow-green PGND wire should bewelded with the angle iron (steel pipe) and the joint should be processedagainst eroding. (For the Switch 8800 Family, the grounding screw is on therear panel. Connect it as illustrated in Figure 38).Figure 39 Ground the switch when allowed to bury grounding body nearby■ If both ground bar and the conditions for burying the grounding body are notavailable, an AC-powered Ethernet switch can be grounded using the PE wireof the AC power supply. In this case, make sure that the PE wire of the AC(1) Air filter (2) Grounding screw(3) PGND wire (4) Ground bar of the equipment room(5) Rear panel of the switch(1) Air filter (2) Grounding screw(3) PGND wire (4) Ground bar of the equipment room(5) Angle steel (6) Rear panel of the switch˄5˅˄1˅˄2˅˄3˅˄4˅˄5˅˄1˅˄2˅˄3˅˄4˅˄5˅˄1˅˄2˅˄3˅˄4˅˄5˅˄1˅˄2˅˄3˅˄4˅˄5˅˄1˅˄2˅˄3˅˄4˅˄5˅˄1˅˄2˅˄3˅˄4˅˄6˅˄1˅˄2˅˄3˅˄5˅˄4˅˄6˅˄1˅˄2˅˄3˅˄5˅˄4˅˄6˅˄1˅˄2˅˄3˅˄5˅˄4˅