8.7.1 IdentificationSEMOD176456-2 v3Function description IEC 61850identificationIEC 60617identificationANSI/IEEE C37.2device numberSingle point generic control 8 signals SPC8GAPC - -8.7.2 Application SEMOD176511-4 v6The Single point generic control 8 signals (SPC8GAPC) function block is acollection of 8 single point commands that can be used for direct commands forexample reset of LED's or putting IED in "ChangeLock" state from remote. In thisway, simple commands can be sent directly to the IED outputs, withoutconfirmation. Confirmation (status) of the result of the commands is supposed tobe achieved by other means, such as binary inputs and SPGAPC function blocks.PSTO is the universal operator place selector for all controlfunctions. Even if PSTO can be configured to allow LOCAL orALL operator positions, the only functional position usable with theSPC8GAPC function block is REMOTE.8.7.3 Setting guidelines SEMOD176518-4 v6The parameters for the single point generic control 8 signals (SPC8GAPC)function are set via the local HMI or PCM600.Operation: turning the function operation On/Off.There are two settings for every command output (totally 8):PulseModex: decides if the command signal for output x is Latched (steady) orPulsed.tPulsex: if PulseModex is set to Pulsed, then tPulsex will set the length of the pulse(in seconds).8.8 AutomationBits, command function for DNP3.0AUTOBITS SEMOD158589-1 v31MRK 511 423-UEN A Section 8ControlBay control REC650 2.2 IEC 165Application manual