Technical specificationsPage 3-14 ABB Control - AC 311SBC 260400 R1001-b 06.994.2. Technical specifications of the extensible remote unitsICMK 14 F1 ICMK 14 F1 ICMK 14 N124 V d.c. 120 / 230 V a.c. 24 V d.c.- Weight 400 g 800 g 400 gPower supply- Mains voltage:Nominal valueAdmissible range24 V d.c.19.2 to 30 V120 or230 V a.c.97.75 to126.5 V or195.5 to 253 V24 V d.c.19.2 to 30 V- Consumption:Unit alone (typical)Maximum configuration (typical)80 mA400 mA30 mA100 mA80 mA400 mA- Polarity reversal protection yes - yes- 24 V d.c. isolated power forthe inputs:Range of voltage valueMax. Output currentShort circuit protectionno---yes19.2 to 30 V400 mAyesno---- Dissipation 5 W 10 W 6 WIncorporated binary inputs- Number of inputs 8 8 8- Isolation of the inputs / electronic 1500 V a.c. 1500 V a.c. 1500 V a.c.- Input types PNP and NPN PNP and NPN PNP and NPN- Input voltage:Nominal valueSignal at 0 (IEC 1131-2)Signal at 1 (IEC 1131-2)24 V d.c.0 to + 5 V+ 15 to + 30 V24 V d.c.0 to + 5 V+ 15 to + 30 V24 V d.c.0 to + 5 V+ 15 to + 30 V- Input current at 24 V d.c.:Inputs Ixx.02 to Ixx.07Inputs Ixx.00 and Ixx.017 mA9 mA7 mA9 mA7 mA9 mA- Minimum filtering time 5 ms 5 ms 5 ms- Cable length:unshieldedshielded300 m500 m300 m500 m300 m500 m