EN – R5 Quick installation guide 35R0-R4R5R6-R9ENDEESFIFRRUSVZHConnect the power cablesSee figures D (page 56), E and R5 Figures F (page 57).1. Attach the residual voltage warning sticker in the local language next to thecontrol board.2. Remove the shroud on the power cable terminals by releasing the clips with ascrewdriver and pulling the shroud out.Use symmetrical shielded cable for motor cabling. If the cable shield is the sole PEconductor for drive or motor, make sure that is has sufficient conductivity for the PE.3. Cut an adequate hole into the rubber grommet. Slide the grommet onto the cable.4. Prepare the ends of the motor cable as illustrated in figures 4a and 4b (twodifferent motor cable types are shown). Note: The bare shield will be grounded360 degrees. Mark the pigtail made from the shield as a PE conductor withyellow-and-green color.5. Slide the cable through the hole in the cable entry and attach the grommet to thehole.6. Connect the motor cable:• Ground the shield 360 degrees by tightening the clamp of the power cablegrounding shelf onto the stripped part of the cable (6a).• Connect the twisted shield of the cable to the grounding terminal (6b).• Connect the phase conductors of the cable to the T1/U, T2/V and T3/Wterminals (6c). Tighten the screws to the torque given in the figure.7. Repeat steps 3…5 for the input power cable.8. Connect the input power cable. Tighten the screws to the torque given in thefigure.9. Install the cable box plate. Position the plate and tighten the screw.10. Reinstall the shroud on the power terminals by putting the tabs at the top of theshroud in their counterparts on the drive frame and then pressing the shroud inplace.11. Secure the cables outside the unit mechanically.12. See figure G (page 57). Ground the motor cable shield at the motor end. Forminimum radio frequency interference, ground the motor cable shield 360degrees at the cable entry of the motor terminal box.