ACS 400 User’s Manual55ACS 400 Complete Parameter ListInitially, only the so called basic parameters (shaded grey in Table 12) are visible. Use theappropriate menu function of the control panel to make the full parameter set visible.S = Parameters can be modified only when the drive is stopped.M = Default value depends on the selected macro (*).Table 12 Full parameter set.Code Name Range Resolution Default User S MGroup 99START-UP DATA9901 LANGUAGE 0 - 12 1 0 ( ENGLISH)9902 APPLIC MACRO 0 - 8 1 0 ( FACTORY ) á9905 MOTOR NOM VOLT 200, 208, 220, 230, 240,380, 400, 415, 440, 460,480 V- 230 V / 400 V á9906 MOTOR NOM CURR 0.5*I N - 1.5*I N 0.1 A 1.0*I N á9907 MOTOR NOM FREQ 0 - 250 Hz 1 Hz 50 Hz á9908 MOTOR NOM SPEED 0 - 3600 rpm 1 rpm 1440 rpm á9909 MOTOR NOM POWER 0.1 - 100 kW 0.1 kW 2 - 30 kW á9910 MOTOR COS PHI 0.50 - 0.99 0.01 0.83 áGroup 01OPERATING DATA0102 SPEED 0 - 9999 rpm 1 rpm -0103 OUTPUT FREQ 0 - 250 Hz 0.1 Hz -0104 CURRENT - 0.1 A -0105 TORQUE - 0.1 %0106 POWER - 0.1 kW -0107 DC BUS VOLTAGE 0 - 999.9 V 0.1 V -0109 OUTPUT VOLTAGE 0 - 480 V 0.1 V -0110 ACS 400 TEMP 0 - 150 °C 0.1 °C -0111 EXTERNAL REF 1 0 - 250 Hz 0.1 Hz -0112 EXTERNAL REF 2 0 - 100 % 0.1 % -0113 CTRL LOCATION 0 - 2 1 -0114 RUN TIME (R ) 0 - 9999 h 1 h -0115 kWh COUNTER ( R) 0 - 9999 kWh 1 kWh -0116 APPL BLK OUTPUT 0 - 100 % 0.1 % -0117 DI 1-DI 4 STATUS 0000 - 1111(0 - 15 decimal)1 -0118 AI 1 0 - 100 % 0.1 % -0119 AI 2 0 - 100 % 0.1 % -0121 DI 5 & RELAYS 0000 - 0111(0 - 7 decimal)1 -0122 AO 0 - 20 mA 0.1 mA -0124 ACTUAL VALUE 1 0 - 100 % 0.1 % -0125 ACTUAL VALUE 2 0 - 100 % 0.1 % -0126 CONTROL DEV -100 - 100 % 0.1 % -