ACS 400 User’s Manual 45Application Macro 3-wireThis macro is intended for those applications where the drive is controlled using momentary push-buttons. It gives two more preset speeds compared to Factory Macro (1) by using DI4 and DI5.Note! The default frequency is 60 Hz.Note! The value of parameter 9902 is 2 (3- WIRE ).*Constant speed selection: 0 = open, 1 = connectedNote! Deactivation of stop signal interlocks panel START/STOP button in local control mode.Application Macro 3-wire parameter values:Input signals Output signals V/I jumper S1• Start,stop and direction(DI1,2,3)• An. output AO: Frequency• Analog reference (AI1) • Relay output 1: Fault• Preset speed selection (DI4,5) • Relay output 2: RunningDI4 DI5 Output0 0 Reference through AI11 0 Constant speed 1 (1202)0 1 Constant speed 2 (1203)1 1 Constant speed 3 (1204)9905 MOTOR NOM VOLT 480 V 1105 EXT REF1 MAX 60 Hz9907 MOTOR NOM FREQ 60 Hz 1106 EXT REF2 SELECT 0 (KEYPAD)9908 MOTOR NOM SPEED 1720 rpm 1201 CONST SPEED SEL 8 (DI4,5)1001 EXT 1 COMMANDS 4 (DI1P,2P,3) 1503 AO CONTENT MAX 60 Hz1002 EXT 2 COMMANDS 0 (NOT SEL) 1601 RUN ENABLE 0 (NOT SEL)1003 DIRECTION 3 (REQUEST) 1604 FAULT RESET SEL 0 (KEYPAD)2008 MAXIMUM FREQ 60 Hz1102 EXT1/EXT2 SEL 6 (EXT1) 2105 PREMAGN SEL 0 (NOT SEL)1103 EXT REF1 SELECT 1 (AI1) 2201 ACC/DEC 1/2 SEL 0 (NOT SEL)AI1:AI2:mA12345678910111213141516171819202122SCRAI1AGND+10VAI2AGNDAO1AGND+24VDCOM1DI1DI2DI3DI4DI5DCOM2RO1CRO1ARO1BRO2CRO2BExternal Reference 1: 0...10 V <=> 0...60 HzReference voltage 10 VDCNot usedOutput frequency 0...20 mA <=> 0...60 Hz+24 VDCMomentary activation with DI2 activated: StartMomentary deactivation: StopActivate to reverse rotation: Fwd/RevConstant speed selection*Constant speed selection*Relay ouput 1, programmableDefault: fault => 17 connected to 18Relay ouput 2, programmableDefault: running => 20 connected to 22RO2A0 -10 V0 -10 V