ACS550-02/U2 User’s Manual 111Application macrosUser parameter setsIn addition to the standard application macros, it is possible to save two userparameter sets into the permanent memory and load them at a later time. A userparameter set consists of the user parameter settings, including Group 99: START-UP DATA, and the results of the motor identification. The panel reference is alsosaved if the user parameter set is saved and loaded in local control. The remotecontrol setting is saved into the user parameter set, but the local control setting isnot.The steps below show how to save and load User Parameter Set 1. The procedurefor User Parameter Set 2 is identical, only the parameter 9902 values are different.To save User Parameter Set 1:• Adjust the parameters. Perform the motor identification if it is needed in theapplication but it is not done yet.• Save the parameter settings and the results of the motor identification to thepermanent memory by changing parameter 9902 to -1 (USER S 1 SAVE ).• Press (Assistant Control Panel) or (Basic Control Panel).To load User Parameter Set 1:• Change parameter 9902 to 0 (USER S1 LOAD ).• Press (Assistant Control Panel) or (Basic Control Panel) to load.The user parameter set can also be switched through digital inputs (see parameter1605).Note: Loading the user parameter set restores the parameter settings includingGroup 99: START-UP DATA and the results of the motor identification. Check thatthe settings correspond to the motor used.Hint: The user can for example switch the drive between two motors without havingto adjust the motor parameters and to repeat the motor identification every time themotor is changed. The user needs only to adjust the settings and perform the motoridentification once for each motor and then to save the data as two user parametersets. When the motor is changed, only the corresponding user parameter set needsto be loaded, and the drive is ready to operate.SAVE ENTERMENUSAVE ENTERMENUPhone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com