Actual signals and parameters21996.06 EXT AO2 PTR Defines the source or constant for value. 1000 =1 mA-255.255.31 …+255.255.31 / C.-32768 … C.32767Parameter index or a constant value. See parameter 10.04 for information onthe difference.-96.07 INVERT EXT AO2 Activates the inversion of analogue output AO2 of the analogue I/O extensionmodule. The analogue signal is at its minimum level when the drive signalindicated is at its maximum and vice versa.NO Inactive 0YES Active 6553596.08 MINIMUM EXT AO2 Defines the minimum value for analogue output AO2 of the analogue I/Oextension module. See parameter 96.03.0 mA 0 mA 14 mA 4 mA 210 mA 10 mA 312 mA 12 mA 496.09 FILTER EXT AO2 Defines the filtering time constant for analogue output AO2 of the analogue I/Oextension module. See parameter 15.04.0.00 … 10.00 s Filtering time constant 0 … 100096.10 SCALE EXT AO2 Defines the scaling factor for analogue output AO2 of the analogue I/Oextension module. See parameter 15.05.10 … 1000% Scaling factor 100 …1000097 MOTOR MODEL97.12 EM STOP DIO Enables emergency stop commands through the RDIO module located on theRMIO board (RDIO-SLOT1 or RDIO-SLOT2) or in the external I/O ModuleAdapter AIMA (RDIO-DDCS).- RDIO digital input 1 (DI1) = OFF2 STOP- RDIO digital input 2 (DI2) = OFF3 STOPThe OFF3 deceleration time is defined by parameter 22.07 EM STOP RAMPTIME.NO Emergency stop through the RDIO module is not in use. 1RDIO-SLOT1 OFF2 STOP (through DI1) and/or OFF3 STOP (through DI2) is taken from theRDIO module located in option SLOT 1.2RDIO-SLOT2 OFF2 STOP (through DI1) and/or OFF3 STOP (through DI2) is taken from theRDIO module located in option SLOT 2.3RDIO-DDCS OFF2 STOP (through DI1) and/or OFF3 STOP (through DI2) is taken from theRDIO module located on the AIMA I/O Module Adapter (RDIO-DDCS).Note: If RDIO-DDCS is selected, the module node number must be set to 7.497.16 SPD CORR PTR Speed correction pointer. Default: +.000.000.00. Defines external speedcorrection by writing it to signal SPEED CORR BUFF (03.35). Speed correctionpointer is to be used only when Synchro control is not used.-255.255.31 …+255.255.31 / C.-32768 … C.32767Parameter index or a constant value.97.17 APL LIM WRN MASK Application limit warning mask. Default 0000 0001 1111 1000 b (binary mode).This parameter can block application messages not required for the controlpanel display.Index Name/Selection Description FbEq