Electrical installation598. Tighten the clamping nuts of the cable glands.After connecting the control cables, fasten the front covers.Warning stickerThere are warning stickers in different languages inside the packing box of the drive.Attach a warning sticker in the language of your choice onto the plastic skeletonabove the power cable terminals.Cabinet installation (IP 21, UL type 1)The drive can be installed in a cabinet without the connection box and front cover.It is recommended:ï to ground the cable shield 360 degrees at the cabinet entryï to lead the cable unstripped as close to the terminals as possible.Secure the cables mechanically.Wire size Compression lug Crimping toolMCM/AWG Manufacturer Type Manufacturer Type No. of crimps6 Burndy YAV6C-L2 Burndy MY29-3 1Ilsco CCL-6-38 Ilsco ILC-10 24 Burndy YA4C-L4BOX Burndy MY29-3 1Ilsco CCL-4-38 Ilsco MT-25 12 Burndy YA2C-L4BOX Burndy MY29-3 2Ilsco CRC-2 Ilsco IDT-12 1Ilsco CCL-2-38 Ilsco MT-25 11 Burndy YA1C-L4BOX Burndy MY29-3 2Ilsco CRA-1-38 Ilsco IDT-12 1Ilsco CCL-1-38 Ilsco MT-25 1Thomas & Betts 54148 Thomas & Betts TBM-8 31/0 Burndy YA25-L4BOX Burndy MY29-3 2Ilsco CRB-0 Ilsco IDT-12 1Ilsco CCL-1/0-38 Ilsco MT-25 1Thomas & Betts 54109 Thomas & Betts TBM-8 32/0 Burndy YAL26T38 Burndy MY29-3 2Ilsco CRA-2/0 Ilsco IDT-12 1Ilsco CCL-2/0-38 Ilsco MT-25 1Thomas & Betts 54110 Thomas & Betts TBM-8 3