54 Start-upStarting up ACS880 drives1. Power up the drive.2. Enable the communication between the adapter module andthe drive by setting parameter 50.01 FBA A enable to Enable.3. With parameter 50.02 FBA A comm loss func, select how thedrive reacts to a fieldbus communication break.Note that this function monitors both communication betweenthe fieldbus master and the adapter module andcommunication between the adapter module and the drive.4. With parameter 50.03 FBA A comm loss t out, define thetime between communication break detection and the selectedaction.5. Select application-specific values for parameters50.04…50.11. Examples of appropriate values are shown inthe tables below.6. Set the FSCA-01 configuration parameters in group 51.• Select the communication protocol with parameter 51.25and profile with parameter 51.02.• Configure the network settings with parameters51.03…51.05.• With parameters 51.06 and 51.07, select how the adaptermodule detects fieldbus communication breaks.7. Define the process data transferred to and from the drive inFSCA-01 configuration parameter groups 52 and 53.Note 1: The adapter module assigns the Control word, Statusword, references 1…2 and actual values 1…2 automatically toModbus registers. Process data groups are not available in theABB Drives - Classic communication profile.