8 ProcessMaster FEP630, HygienicMaster FEH630 ELECTROMAGNETIC FLOWMETER | SI/FEP630/FEH630/FM/CSA-EN REV. A… 2 Device designsVersion with remote mount designThe transmitter is mounted in a separate location from the flowmeter sensor. The electrical connection between the transmitter andflowmeter sensor may only be established using the signal cable supplied.A maximum signal cable length of 200 m (656 ft) is possible.NoteFurther information on the Ex Approval of devices can be found in the type examination certificates or the relevant certificates atwww.abb.com/flow.DIV. 1DANGERExplosion hazard caused by incorrect transmitter installationThe FET632-Y0 transmitter does not have Ex Approval.The FET632-Y0 transmitter may not be installed and operated in potentially explosive atmospheres.The following table presents the combination of the FEP632, FEH632 sensor in explosion-proof design with the FET632 transmitter.SensorProcessMaster 630 HygienicMaster 630FEP632-F1 FEH632-F1in Ex area, Div. 1 in Ex area, Div. 1USA, FM approval USA, FM approvalCertificate: FM17US0062X Certificate: FM17US0062XDN3-300:S-XP-IS: CL I, Div 1, GPS BCD T6...T1DIP: CL II,III, Div 1, GPS EFG T6...T3BDN3-100:S-XP-IS: CL I, Div 1, GPS BCD T6...T1DIP: CL II,III, Div 1, GPS EFG T6...T3B>DN300:CL I, ZN 1, AEx db eb mb [ia Ga] IIB+H2 T6…T1 GbZN 21, AEx tb [ia Da] IIIC T80°C...T165°C DbCanada, cFM approval Canada, cFM approvalCertificate: FM17CA0033X Certificate: FM17CA0033XDN3-300:S-XP: CL I, Div 1, GPS BCD T6...T1DIP: CL II,III, Div 1, GPS EFG T6…T3BDN3-100:S-XP: CL I, Div 1, GPS BCD T6...T1DIP: CL II,III, Div 1, GPS EFG T6…T3B>DN300:CL I, ZN 1, Ex db eb mb IIB+H2 T6…T1 GbEx tb IIIC T80°C...T165°C Db