Settable time limits for warning and alarm are provided. The time limit foroverflow indication is fixed to 999999.9 seconds.16.12.3 Setting guidelines GUID-2911D624-87D5-4427-BB2F-E0D1072394FA v3The settings tAlarm and tWarning are user settable limits defined in seconds. Theachievable resolution of the settings depends on the level of the values defined.A resolution of 10 ms can be achieved when the settings are defined within therange1.00 second ≤ tAlarm ≤ 99 999.99 seconds1.00 second ≤ tWarning ≤ 99 999.99 seconds.If the values are above this range, the resolution becomes lower due to the 32 bitfloat representation99 999.99 seconds < tAlarm ≤ 999 999.0 seconds99 999.99 seconds < tWarning ≤ 999 999.0 secondsNote that tAlarm and tWarning are independent settings, that is,there is no check if tAlarm > tWarning.The limit for the overflow supervision is fixed at 999999.9 seconds.16.13 Comparator for integer inputs - INTCOMP16.13.1 Identification GUID-5992B0F2-FC1B-4838-9BAB-2D2542BB264D v1Function description IEC 61850identificationIEC 60617identificationANSI/IEEE C37.2device numberComparison of integer values INTCOMP Int<=>16.13.2 Application GUID-4C6D730D-BB1C-45F1-A719-1267234BF1B9 v1The function gives the possibility to monitor the level of integer values in thesystem relative to each other or to a fixed value. It is a basic arithmetic functionthat can be used for monitoring, supervision, interlocking and other logics.1MRK 511 401-UEN A Section 16LogicBay control REC670 2.2 IEC 469Application manual