Displays up to two instances of CCRPLD with two measurements per instancewhich contain trip and start data.11.6.3.9 Four step residual overcurrent protection EF4PTOCTest/Function status/Current protection/ResidualOverCurrent4Step(PTOC,51N_67N)/TEFDisplays available instances of EF4PTOC with a number of measurements perinstance. The measurements indicate trip and start signal status as well as the 2ndharmonic block signal status.11.6.3.10 Sensitive directional residual over current and power protectionSDEPSDEMain menu/Test/Function status/Current protection/SensDirResOvCurr(PSDE,67N)/SDEDisplays the output data of SDEPSDE.11.6.3.11 Stub protection STBPTOCMain menu/Test/Function status/Current protection/Stub(PTOC,STB)/STBDisplays available instance of STBPTOC with a number of measurements thatinclude trip and start data.11.6.3.12 Thermal overload protection, one time constant LPTTRMain menu/Test/Function status/Current protection/ThermalOverload1TimeConst(PTTR,26)/THLDisplays available instances of LPTTR with a number of measurements perinstance. The measurements show temperature data, trip status, lockout and time tolockout.11.6.3.13 Thermal overload protection, two time constants TRPTTRMain menu/Test/Function status/Current protection/ThermalOverload2TimeConst(PTTR,49)/TTRDisplays available instances of TRPTTR with a number of measurements perinstance. The measurements show trip data, start signal status, time to reset, alarmsignals and others.1MRK 511 188-UEN C Section 11Test the IED73Operator's manual