Table 8:Analog input interfaceHardware moduleinstanceHardware channel UsageAIM_2 CH1 Line-side current, IL1AIM_2 CH2 Line-side current, IL2AIM_2 CH3 Line-side current, IL3AIM_2 CH4 Differential neutral current, I0AIM_2 CH5 Neutral-side current, IL1_NAIM_2 CH6 Neutral-side current, IL2_NAIM_2 CH7 Neutral-side current, IL3_NAIM_2 CH8 Line-side voltage, U1AIM_2 CH9 Line-side voltage, U2AIM_2 CH10 Line-side voltage, U33.2.4 Preprocessing blocks and fixed signalsThe analog current and voltage signals coming to the IED are processed bypreprocessing blocks. A preprocessing block with two different task times isavailable. All the function blocks functioning at 3 ms task time must be connectedwith a preprocessor operating at 3 ms. Similarly, all the function blocks functioning at10 ms task time must be connected with a preprocessor operating at 10 ms.The preprocessor calculates various quantities based on an adaptive DFT. Theadaptive DFT requires a reference frequency for performing calculations. In thisconfiguration, the voltage signals are taken as reference for calculating various phase-side and neutral-side current quantities.See the technical manual for details on frequency adaptive.A fixed signal block providing logical TRUE and FALSE output is used, andconnected internally to other functional blocks as needed.3.2.5 Control functions3.2.5.1 Generator bay control QCCBAYBay control is used for handling the selection of the operator place per bay. It providesblocking functions that can be distributed to different apparatus within a bay. Baycontrol sends information about the PSTO and blocking conditions to other functionswithin the bay, such as to switch control functions.Section 3 1MRS757582 CREG630 variants28 REG630Application Manual