3.2.9 Binary recording and LED configurationAll the start and operate outputs from the respective protection functions, variousalarms from supervision functions, and important signals from control and protectivefunctions are connected to a binary recorder. In case of a fault, the binary recorder istriggered and all the signals connected to the recorder are recorded.Table 10:Signals connected to binary recorderChannel ID DescriptionChannel 1 Operate of differential protection high stageChannel 2 Operate of differential protection low stageChannel 3 Differential protection internally blockedChannel 4 Start of overcurrent low stageChannel 5 Operate of overcurrent low stageChannel 6 Start of overcurrent high stageChannel 7 Operate of overcurrent high stageChannel 8 Start of voltage controlled overcurrent stage 1Channel 9 Operate of voltage controlled overcurrent stage 1Channel 10 Start of voltage controlled overcurrent stage 2Channel 11 Operate of voltage controlled overcurrent stage 2Channel 12 Start of negative sequence overcurrent stage 1Channel 13 Operate of negative sequence overcurrent stage 1Channel 14 Start of negative sequence overcurrent stage 2Channel 15 Operate of negative sequence overcurrent stage 2Channel 16 Thermal overload prior alarmChannel 17 Operate thermal overloadChannel 18 Start of directional earth fault low stageChannel 19 Operate of directional earth fault low stageChannel 20 Start of directional earth fault high stageChannel 21 Operate of directional earth fault high stageChannel 22 Start of phase overvoltage protection stage 1Channel 23 Operate of phase overvoltage protection stage 1Channel 24 Start of phase overvoltage protection stage 2Channel 25 Operate of phase overvoltage protection stage 2Channel 26 Start of phase undervoltage protection stage 1Channel 27 Operate of phase undervoltage protection stage 1Channel 28 Start of phase undervoltage protection stage 2Channel 29 Operate of phase undervoltage protection stage 2Channel 30 Start of residual overvoltage protection stage 1Channel 31 Operate of residual overvoltage protection stage 1Channel 32 Start of residual overvoltage protection stage 2Table continues on next page1MRS757582 C Section 3REG630 variantsREG630 47Application Manual