tClosePulse is the output pulse length for a close command. If AdaptivePulse is set toAdaptive, it is the maximum length of the output pulse for an open command. The defaultlength is set to 200 ms for a circuit breaker (SXCBR) and 500 ms for a disconnector(SXSWI).15.3.3.4 Proxy for signals from switching device via GOOSE XLNPROXYThe SwitchType setting controls the evaluation of the operating capability. If SwitchTypeis set to Circuit Breaker, the input OPCAP is interpreted as a breaker operating capability,otherwise it is interpreted as a switch operating capability.Table 51:Operating capability values for breaker/switchesValue Breaker operating capability, CbOpCap Switch operating capability, SwOpCap1 None None2 Open Open3 Close – Open Close4 Open – Close – Open Close and Open5 Close – Open – Close – Open Larger values handled as 4, both Close and Open6 Open – Close – Open – Close – Open7 moretStartMove is the supervision time for the apparatus to start moving after a commandexecution is done from the SCSWI function. When the time has expired, the commandsupervision is reset, and a cause-code is given.During the tIntermediate time, the position indication is allowed to be in an intermediate(00) state. When the time has expired, the command supervision is reset, and a cause-codeis given. The indication of the mid-position at SCSWI is suppressed during this timeperiod when the position changes from open to close or vice-versa if the parameterSuppressMidPos is set to On in the SCSWI function.In most cases, the same value can be used for both tStartMove and tIntermediate as in thesource function. However, tStartMove may need to be increased to accommodate for thecommunication delays, mainly when representing a circuit breaker.15.3.3.5 Bay Reserve (QCRSV)The timer tCancelRes defines the supervision time for canceling the reservation, when thiscannot be done by requesting bay due to for example communication failure.When the parameter ParamRequestx (x=1-8) is set to Only own bay res. individually foreach apparatus (x) in the bay, only the own bay is reserved, that is, the output forSection 15 1MRK 506 369-UUS -Control698 Line distance protection REL670 2.2 ANSIApplication manual