ApplicationGeneric communication function for Single Point Value (SPGAPC) function is used tosend one single logical output to other systems or equipment in the substation. SP16GAPCcan be used to send up to 16 single point values from the application functions running inthe same cycle time. SPGAPC has one visible input and SPGAPC16 has 16 visible inputsthat should be connected in the ACT tool.Setting guidelinesThere are no settings available for the user for SPGAPC.Generic communication function for Measured Value MVGAPCApplicationGeneric communication function for measured values (MVGAPC) function is used tosend the instantaneous value of an analog signal to other systems or equipment in thesubstation. It can also be used inside the same IED, to attach a RANGE aspect to an analogvalue and to permit measurement supervision on that value.Setting guidelinesThe settings available for Generic communication function for Measured Value(MVGAPC) function allows the user to choose a deadband and a zero deadband for themonitored signal. Values within the zero deadband are considered as zero.The high and low limit settings provides limits for the high-high-, high, normal, low andlow-low ranges of the measured value. The actual range of the measured value is shownon the range output of MVGAPC function block. When a Measured value expander block(RANGE_XP) is connected to the range output, the logical outputs of the RANGE_XP arechanged accordingly.21.2.3.2 Receiving dataThe GOOSE data must be received at function blocks. There are different GOOSEreceiving function blocks depending on the type of the received data. Refer to theEngineering manual for more information about how to configure GOOSE.Function block type Data TypeGOOSEBINRCV 16 single pointGOOSEINTLKRCV 2 single points16 double pointsGOOSEDPRCV Double pointGOOSEINTRCV IntegerGOOSEMVRCV Analog valueGOOSESPRCV Single pointGOOSEXLNRCV Switch statusSection 21 1MRK 506 369-UUS -Station communication866 Line distance protection REL670 2.2 ANSIApplication manual