GUID-1253B0CE-98D9-48BB-91B6-ADF29EC2CD7E V1 ENFigure 94: Creating a state6.1.6 SLD EditorSLD Editor is used to create single-line diagrams. In SLD Editor, bus bars, symbolsand text can be added from the object type window and links can be created betweensymbols.Once the symbols are placed on the HMI page, they must be linked in ApplicationConfiguration to the corresponding function block that protects or controls the objectrepresented by the symbol. The values are updated by the protection relay eitherperiodically (measurement) or in case of an event.Single-line diagrams support both ANSI and IEC standards. Single-line diagramscreated in ANSI can be changed to IEC and vice versa by changing the symbolstandard in PCM600. Custom symbols can be used in both ANSI and IEC standards.In the object type window, symbols are grouped by their category.The single-line diagram created in SLD Editor can be used on the main pages with aspecial widget called SLDViewPort. The widget is available under the Containergroup and its page property populates the list of SLD pages. The single-line diagramsize can be selected from the Object Properties pane. In ViewPort the single-linediagram can be zoomed and paned on the LHMI.Section 6 1MRS759117 ALHMI engineering114 REX640Engineering Manual