Section 9 1MAC309294-MB FOther functions446 RER620Technical ManualTable 400: PTGAPC Output signals9.5.4 SettingsTable 401: PTGAPC Non group settingsTable 402: Generic timers, TPGAPC1...4Table 403: Generic timers, TPSGAPC1Table 404: Generic timers, TPMGAPC19.5.5 Technical dataTable 405: PTGAPC Technical dataName Type DescriptionQ1 BOOLEAN Output 1 statusQ2 BOOLEAN Output 2 statusQ3 BOOLEAN Output 3 statusQ4 BOOLEAN Output 4 statusQ5 BOOLEAN Output 5 statusQ6 BOOLEAN Output 6 statusQ7 BOOLEAN Output 7 statusQ8 BOOLEAN Output 8 statusParameter Values (Range) Unit Step Default DescriptionPulse delay time 1 0...3600000 ms 10 0 Pulse delay timePulse delay time 2 0...3600000 ms 10 0 Pulse delay timePulse delay time 3 0...3600000 ms 10 0 Pulse delay timePulse delay time 4 0...3600000 ms 10 0 Pulse delay timePulse delay time 5 0...3600000 ms 10 0 Pulse delay timePulse delay time 6 0...3600000 ms 10 0 Pulse delay timePulse delay time 7 0...3600000 ms 10 0 Pulse delay timePulse delay time 8 0...3600000 ms 10 0 Pulse delay timeParameter Values (Range) Unit Step Default DescriptionPulse time 0...60000 ms 1 150 Minimum pulse timeParameter Values (Range) Unit Step Default DescriptionPulse time 0...300 s 1 0 Minimum pulse time, range in secondsParameter Values (Range) Unit Step Default DescriptionPulse time 0...300 min 1 0 Minimum pulse time, range in minutesCharacteristic ValueOperate timeaccuracy±1.0% of the setvalue or ±20 ms