7.4.17 Overvoltage PTOVLN type LN prefix LN class Function block nameNSPTOV (revision 0) NS PTOV NSPTOVTable 99:NSPTOV Logical node dataDO name DO type DA name FC T Signal Mon/CmdDescriptionMod a_dINC Oper.ctlVal CO - - Cmd Mode parameter for 61850Oper.origin.orCat CO - - Cmd Mode parameter for 61850Oper.origin.orIdent CO - - Cmd Mode parameter for 61850Oper.ctlNum CO - - Cmd Mode parameter for 61850Oper.T CO - - Cmd Mode parameter for 61850Oper.Test CO - - Cmd Mode parameter for 61850Oper.Check CO - - Cmd Mode parameter for 61850stVal ST - - Mon Mode status parameter for 61850q ST - - Mon Quality: Mode status parameter for61850t ST - - Mon Timestamp: Mode statusparameter for 61850Beh a_dINS stVal ST - Beh Mon Behaviour parameter for 61850q ST - Beh Mon Quality: Behaviour parameter for61850t ST - Beh Mon Timestamp: Behaviour parameterfor 61850Op b_dACT general ST T OPERATE Mon Operate signal for NegativeSequence Overvoltage logicq ST T OPERATE Mon Quality: Operate signal forNegative Sequence Overvoltagelogict ST T OPERATE Mon Timestamp: Operate signal forNegative Sequence OvervoltagelogicStr d_dACD general ST - START Mon Start signal for NegativeSequence Overvoltage logicq ST - START Mon Quality: Start signal for NegativeSequence Overvoltage logict ST - START Mon Timestamp: Start signal forNegative Sequence OvervoltagelogicStrDur v2_dMV mag.f MX - START_DUR Mon Start duration in percentage of thetotal operating timeq MX - START_DUR Mon Quality: Start duration inpercentage of the total operatingtimet MX - START_DUR Mon Timestamp: Start duration inpercentage of the total operatingtime1MRS756793 E Section 7Logical node data model630 series 143Communication Protocol Manual