symbol can be changed either by double click the symbol or via the object propertywindow.Select and toggle Show Texts using the IED Fonts to get a view how it will looklike later on the real HMI display.Doing Link to draw linesThe line width has to fit to the line width used for the symbols. The standard size is2. Choose the line width in a selection box placed in the upper area above the page.A line that is not connected to a symbol may be done in any line width in the range1 - 5. But it needs to be simple connection points to be drawn.Procedure to draw lines when the apparatus symbols are placed, see Figure 48:1. Place the apparatus or transformer symbols by drag and drop in a raster box.2. Place the connections symbols by drag and drop in a raster box.3. Click the Link icon to enable direct line drawing.4. Center the mouse pointer on the center of a connection point; visible in twocircles at the endpoints of a line, to draw a line.5. Click to start and move the mouse pointer to the destination connection point.Center once again the mouse pointer and click to drop the line.6. Draw all line elements that are necessary.7. Click Select in the menu bar to finish the line drawing.en05000598.vsdstart point end pointLine draw iconIEC05000598 V1 ENFigure 48: GDE: Drawing a line6.2.2 Bay configuration engineeringA page with a single line diagram and measurements contains active living objects.The object values are updated by the IED periodically (measurement) or in case ofan event. Once the symbols are placed on the HMI page they must be linked to the1MRK511240-UEN B Section 6Local HMI engineering670 series 65Engineering Manual